background image

WARNING: 

Disconnect  all power  from  the  starter  and 

overload  relay  before  installing,  modifying,  or 

servicing. 

AVERTISSEMENT: 

Couper  l'alimentation 

installation,  modific-ation,  ou  entretien. 

avant 

CAUTION: 

Before  installing  this  product in  a nuclear 

application,  determine  if  it  is intended  for  such use. 

ATTENTION: 

Avant  d'installer  le  produit  dans  une 

application  nucleaire,  verifier  si  cela  est  permis. 

Introduction 

The  ABB  Solid  State  Overload  Relay  is  shown  in 

Figure  I.  The  catalog  numbers  and  electrical 

specifications are  listed  in  Table  1. 

Replacement  Installation 

The  following  instructions  describe  the  installation  of 

a Solid  State  Overload  Relay  as  a  replacement  for  an 

existing  overload  relay  on  a  300-Line  starter. 

1. Disconnect all sources of power to  the starter.
2. Disconnect  all  control  and  power  wiring  from

the  load  side  of  the existing  overload  relay.

3.

Remove  and  save  the  overload  relay  mounting

screw,  located  at  the  bottom right  and  upper  left

corners  of the  overload  relay  housing.

4.

Remove  the  overload  relay  from  the  starter

baseplate.

5.

Reassemble  the  Solid  State  9verload  Relay  from

this  kit  in  the  reverse order.

Catalog  Number: 

Current 

Replacement 

NEMA  Range, 

Starter Mount 

Size 

amps 

CR324GXNS 

32-68

CR324GXPS 

65-135

CR324GXQS 

130-270

CR324HXSS 

130-270

CR324HXTS 

260-540

Figure  1.  Solid State Overload Relay (external current transformers 

not shown). 

6.

Check  to  see  that  the  two  wires  from  each

current  transformer  have  been  reconnected  to

the  top and  bottom  terminals  on  the  same  pole

of  the  Solid  State  Overload  Relay  as  on  the

overload  relay  that was  replaced.

7. Torque  the  bottom  terminal  screws  to  20 lb-in

and  the  top  terminal  screws  to  12  lb-in.

8.

Connect  the  control  and  power  wiring  to  the

terminals  on  the  load  side  of  the  Solid  State

Overload  Relay,  shown  in  Figure  2.

9.

Reconnect power sources to the starter.

10.

Fully  depress  the  blue reset  button on  the  Solid

State  Overload  Relay  to insure  that  it  is  in  the

reset  position.  The  yellow  trip flag  will  be at its

right  position,  as illustrated  in Figure  2.

Max  Fuse  Size,  Max Breaker  Use  with 

amps  (Class 

Rating, 

ABB 

T ,H,J ,L,R,K) 

amps 

Contactor 

250 

250 

CR306G 

500 

400 

CR306G 

800 

800 

CR306G 

800 

800 

CR306HH 

1600 

1600 

CR306HH 

NOTE: Maximum fuse and breaker sizes are intended as guidelines. Refer to NEC and local codes for proper fuse and 

breaker selection. 

Table 1.  Solid State Overload Relay, NEMA Sizes 5 

6, catalog numbers and electrical specifications. 

GEH

-

6432 User's Guide

Solid State Overload Relay

 

NEMA Sizes 5 & 6 

Отзывы: