background image

Tamper-Resistant  Full-Load Current

Cover 

Adjustment Dial 

Protection Class 

S  itch 

Remote Reset 

Pocket 

Current Transformer 

Trip Indicator &Manual 

Trip Test Lever 

(shown in ON position) 

Terminals (bottom) 

Figure 2.  Top face of Solid State Overload Relay,  with controls and 

features indicated. 

Adjusting  the Solid State Overload 

Relay 

The  following  adjustments  to  the  Solid  State Overload 

Relay  are  illustrated  in  Figure  2.  The  adjustments 

should be  performed  in  the  following  order. 
The  settings  as  the  unit  is  received  from  the  factory 

are  as  follows: 

• Full-load  current  at  minimum.

• Protection class at 20.

Full-Load  Current Adjustment 

This  setting  is  the  current  beyond  which  the  Solid 

State  Overload  Relay  will  trip.  Use  the  following 

guidelines  to  determine  the appropriate  setting: 

• For motors with a service factor of 1.0,  set  the  full­

load current on  the  Solid  State Overload  Relay  to

0.9  times  the  full-load  amps  (FLA)  rating  on the

motor's  nameplate.

• For  motors  with  a  service  factor  of  1.15-1.25,  set

the  full-load  current  on  the  Solid  State  Overload

Relay  to  the  FLA  rating  on  the  motor's

nameplate.

Press on  the tamper-resistant  cover above the FLA dial, 

then  lift  up near  the  tab on  the  other  side  to  remove 

the cover.  Rotate the FLA dial so  that the arrow on  the 

dial  points  to the  desired  current,  as  indicated  by  the 

ampere  markings  around  the  dial.  Do  not rotate past 

the  marked  area.  The  knob  moves  in  small  steps  to 

allow  precise  adjustment  of  the  full-load  current. 

Replace  the  tamper-resistant  cover  to  provide  addi-

tional  dust protection. To protect against  unauthorized 

persons'  tampering  with  the  settings,  insert  a  wire 

lock  through  the  locking  tabs. 

Phase Loss Sensitivity 

The  Solid  State  Overload  Relay  contains  a trip function 

activated by a phase loss. This protection is activated when 

one phase loses current and either one of the remaining 

phase currents exceeds 95% of the minimum FLA of the 

Overload Relay. A phase loss trip occurs within 3-6 seconds 

of loss of phase current. 

Protection  Class Setting 

CAUTION: 

The  slide  switch  must  be  in  one  of  the 

three  detent  positions.  If  the  slide  is  between  one  of 

the detents,  the default  is  protection class  30. 

AITENTION: 

Le  bouton de  selection  de  la  classe  de 

protection doit  etre dans une des trois  positions  stables. 

Si le bouton se trouve entre  deux positions,  la  classe  de 

protection est fixee a 30 par default. 
Set  the  desired  protection  class  to  10,  20,  or  30  by 

sliding  the  switch  to the  appropriate  detent  position. 

The  time-current  curves for  the  protection  classes  are 

shown  in  Figure  3.  Select the class  appropriate to the 

particular  application. 

1000 

iii 

,:, 

¥ 

100 

� 

j:: 

Cl) 

·a

�  10 

I,. 

,'\. 

��

� 

-

..... 

-

-

..__ 

""""" 

........ 

---

-....i,,... 

1--...... 

............... 

1-.............. 

--

... 

r---,...... 

-..............,

--

.......... 

r-

r--

r-,... 

-

Class 30 

Class 20 

Class 10 

6  7  8  9  10 

Multiples of Full Load Amps setting 

Figure 3.  Time-current curves (cold state) for the protection classes. 

Test 

for  Welded  Contacts 

The  following 

procedure  can  be 

performed 

periodically  to  insure  that  the  Solid  State  Overload 

Relay  contacts  have  not  welded  because  of  a  short 

circuit in the  control  circuit. 

1. Disconnect  all  power  and  control  wiring  from

the Solid State  Overload  Relay.

2. Place  a  bell  set  or  resistance-measuring

instrument  across  the  NC  relay  terminals  (95

and  96).

Отзывы: