background image

RGM-12S

USER MANUAL

www.tense.com.tr

www.tenseenerji.com

ELEKTRİK - ELEKTRONİK SAN.TİC.A.Ş.

Содержание RGM-12S

Страница 1: ...RGM 12S USER MANUAL www tense com tr www tenseenerji com ELEKTRİK ELEKTRONİK SAN TİC A Ş ...

Страница 2: ...Compensation Harmonic Voltage Harmonic Current High Voltage Blocking Access to Settings Returning to Factory Settings Fan and Alarm Output Capacitor Calculation Table According to Connection Type Factory Set Values Dimensions Technical Specifications Contact Informations 11 Step Values Considerations in Current Transformer Selection and Connection 3 3 4 5 6 7 Device Maintenance Connection Diagram ...

Страница 3: ...ent Voltage and Current Harmonic Alarm Values Adjustable Over and Under Compensation Alarm Values Can Be Set Voltage Harmonic Voltage Current Over and Under Compensation Alarm Output Step Drive Release and Discharge Times are Adjustable Up to the 15th harmonic THD I Can Be Monitored Voltage Current and Frequency Values Can Be Monitored Active Power Reactive Power and Apparent Power Values Can be M...

Страница 4: ...Use compensation contactors and discharge coils in the steps Single phase connection in three phase systems is only suitable for balanced load draws Otherwise the desired rates will not be achieved Warnings Use the device in accordance with the instructions set by us After the device is mounted leave a space of at least 10 cm behind it Fix the device to the front cover of the panel with the accomp...

Страница 5: ... before the current transformers Otherwise there will be differences in consumption and rates between the device and the electricity meter The current transformer must be connected to the phase from which the voltage input of the device is received Otherwise the device will not be able to perform the current transformer test Current transformer output cables should not be close to the high voltage...

Страница 6: ...1 k1 Steps 1 to 7 Harmonic Filter Capacitor Thermal A2 2A 6A A1 L C1 C2 C3 C4 C5 C6 Steps 8 to 12 L C8 C9 C10C11C12 Harmonic Filter Capacitor Thermal A2 2A 6A A1 C7 Fan and Alarm Outputs L FAN 6A A2 2A A1 ALR Fan A2 2A A1 Alarm Contactor Contactor Contactor Contactor To Load ...

Страница 7: ...on values this LED will light 7 Buttons They are used for monitoring measurements and making settings 8 Measurments Settings LEDs Indicates that the device is in the measurement or setting menu 9 Value Parameter LEDs When the device is in the measurement menu it informs that the measured value is displayed on the screen and the parameter is displayed while in the setting menu 4 Compensation Mode L...

Страница 8: ...MENTS led is on the following measurement values will be displayed sequentially Pressing the up button will display the previous measurement parameter While showing these values the led for the related measurement value lights up Figure 1 It shows the cosine value Figure 2 It shows the current value Figure 3 It shows the voltage value Figure 4 It shows the frequency value Figure 5 It shows the act...

Страница 9: ...u and reach the relevant parameter with the help of up down buttons Then press the SET button to enter the relevant parameter when you enter the parameter the led of the parameter will start to blink Then adjust the value you want with the up down buttons and press the SET button to save it The device will save the value and return to the upper menu After this process the parameter led will stop f...

Страница 10: ...ogram The device has 7 different compensation programs The first 6 of these modes operate automatically and when one of these modes is activated the AUTO led on the device turns on The 7th mode is manual program and works in manual mode When this mode is active the MANUAL led on the device lights up In order to change the program when you press the ESC button for 5 seconds while on the measurement...

Страница 11: ...teps should be at the lowest value in the first step and at the highest value in the last step From small to large value Compensation is not made according to the step value therefore there is no need for step measurement When the step is to be activated it always starts with the first step and activates the other steps one by one When the step is to be deactivated it always starts with the first ...

Страница 12: ...r test again after eliminating the error Err1 Error If you get an Err1 error in the current transformer test there may be a loose contact in the current transformer output connections s1 k and s2 l Check the connections and perform a current transformer test again after eliminating the error 8 8 8 8 E r r 3 Err3 Error If you get an Err3 error in the current transformer test it means there is an er...

Страница 13: ...ights up steadily Example If the Current Transformer Value is 100 5A the ratio value to be entered in Pr1 is 20 100 5 20 Monitoring Step Values In order to see the step values that the device measures automatically press the SET button for 2 seconds while on the measurement screen while MEASUREMENTS led is on When you enter the setting menu the MEASUREMENTS led will turn off and the SETTINGS led w...

Страница 14: ...s the SET button to save the measured value then exit the menu by pressing the ESC button Also press the ESC button to cancel the operation during the measurement and return to the previous menu without saving the value after the measurement is completed Measuring All Steps To have all the steps measured switch between the steps by pressing the DOWN button When you press the DOWN button again afte...

Страница 15: ...life of contactors capacitors and reactors in the steps The device will not change its current intervention for reactive power changes within the Cosine SET Value Cosine Tolerance Value area In order to change the cosine tolerance value press the SET button for 2 seconds while on the measurement screen while MEASUREMENTS led is on When you enter the setting menu the MEASUREMENTS led will turn off ...

Страница 16: ...blink it lights up steadily 8 8 8 8 9 8 5 8 8 8 8 9 8 5 8 8 8 8 3 SET 2sec 8 8 8 8 5 SettingsE Step Release Time Adjusting the Step Release Time It determines the time to release the active step in order to intervene in the power change in the system In order to change this value press the SET button for 2 seconds while on the measurement screen while MEASUREMENTS led is on When you enter the sett...

Страница 17: ...es while the alarm and SETTINGS leds are constantly lit When the cosine value returns to the normal level for 10 seconds the device disables the overcompensation error the alarm relay is deactivated the alarm and OVER led turn off the cosine led turns on In order to change this value press the SET button for 2 seconds while on the measurement screen while MEASUREMENTS led is on When you enter the ...

Страница 18: ...T 2sec 8 8 8 8 0 0 1 5 SettingsE Harmonic Voltage Adjusting the THD V Value If the Total Harmonic Distortion Voltage THD V value stays above the THD V Set value for 15 seconds the device enters a THD V error it stops compensation the alarm relay isenergized it deacitivates all steps the alarm led turns on and the THDV led Pr10 THD V Set flashes When the THD V value stays below 3 of the THD V set v...

Страница 19: ...it lights up steadily 8 8 8 8 9 8 5 8 8 8 8 9 8 5 8 8 8 8 3 0 SET 2sec 8 8 8 8 3 5 SettingsE High Voltage Adjusting the High Voltage Value If the Voltage value stays above the High Voltage Set value for 5 seconds the device enters a High Voltage error it stops compensation the alarm relay isenergized it deacitivates all steps the alarm led turns on and the High Voltage led Pr12 High Voltage flashe...

Страница 20: ...and SET buttons for 5 seconds while on the measurement screen while MEASUREMENTS led is on B on will appear and the feature will be inactive When this feature is disabled it is possible to enter the setting menu 8 8 8 8 9 8 5 8 8 8 8 9 8 5 8 8 8 8 b o f f SET ESC 5sec Settings E Returning to Factory Settings Returning to Factory Settings In order to return the factory settings press the SET button...

Страница 21: ...15 KVAR 20 KVAR 25 KVAR 30 KVAR 3 Phase Connection Q 3 Capacitor Powers 0 16 KVAR 0 33 KVAR 0 5 KVAR 0 83 KVAR 1 66 KVAR 2 5 KVAR 3 33 KVAR 5 KVAR 6 66 KVAR 8 33 KVAR 10 KVAR R S T Phase Netural Connection Q 6 0 08 KVAR 0 16 KVAR 0 25 KVAR 0 41 KVAR 0 83 KVAR 1 25 KVAR 1 66 KVAR 2 5 KVAR 3 33 KVAR 4 16 KVAR 5 KVAR S N ...

Страница 22: ...Fixed Fixed Fixed Fixed Fixed Harmonic Voltage Delay Exiting the Error State Delay To Enter the Error State High Voltage A P Delay Exiting the Error State Passive 15 15 270 5 1 Off 240 400 270 sec V sec sec It can be active or passive A P Voltage Settings Harmonic Voltage Settings Menu Program Auto Otomatik Rot1 Rot2 Rot3 Rot4 Baştan al baştan bırak ve Manuel Operating Mode The value cannot be cha...

Страница 23: ...21 Dimensions 138mm 147mm 114 5mm 147mm 138mm Rear view 147mm Front view 147mm Left side view 138mm 43mm 22mm Side ear apparatus Screwed side ear apparatus 45mm 34mm 6mm 143mm ...

Страница 24: ...Accuracy 100V 300VAC 50 60 Hz 10VA 20ºC 55ºC 30ºC 80ºC 90 Without condensation 10mA 5 5A 20mm 4 Digit LED Display and Notification LEDs 1 5mm 2 5mm Voltage and C T connections 12 Mounting on the panel front cover 2000metre 900Gr IP41 Front Panel IP20 Body 140mm x 140mm Plug in terminal connection 3A 250V AC Resistive Load 10V 300V AC 5 5A 9995 5A 1 1 2 2 Contact Information Muratpaşa Mh Uluyol Cd ...

Страница 25: ...User Notes ...

Страница 26: ...ELEKTRİK ELEKTRONİK SAN TİC A Ş Document Number DK 105 1 Rev 1 00_210505 QUALITY SOLUTIONS MADE IN TURKEY Energy and Compensation Tracking System www tenseenerji com ...

Отзывы: