background image

-- -,;;:;;:;::--- ----;;:;:;>"---·---�----,----

I.  L.  41-600.3 

O

P

E

R

A

T

 

O

N

  O

F

  S

C

H

E

M

E

 

INSTRUCTIONS 

TYPE  HKB  CARRIER  BELAYING 

INTRODUCTION 

The  high-speed 

clearing  of  faults  on  trans­

mission  lines  is 

recognized  as 

necessary  for 

good 

system  operation. 

The 

best 

overall 

protection 

is  provided  by  th�  method  known  as 

differential  relaying  in  which  conditions  at 

the  two  ends 

of  the  line 

are  compared  to  de­

termine 

whether 

the  fault 

is  in  the  line 

section 

or  external  to  the 

protected "'  zone. 

This  assures  simultaneous 

tripping 

of 

the 

breakers, 

which  is  desirable  from  the 

stand­

points  of  stability, 

continuity 

of  service, 

quick  reclosing, 

and  minimum  damage  to  equip­

ment. 

For  many  lines,  carrier  relaying  is  the 

most  practical 

and  reliable 

medium 

for  com­

paring  the  conditions 

at 

the  two  ends  of  the 

line. 

system 

relay 

of  carrier  protection 

operating 

(

on  current 

The  type 

HKB 

uses 

a  single 

only

at 

each 

end 

of  the  transmission  line 

section  to  detect  and  determine  the 

location 

of  faults. 

It  compares  over 

carrier 

pilot 

channel  the  phase  angle  between 

the  two  ends  of  a  line  section 

currents 

at 

to  determine 

whether 

an  internal  or  external  fault  exists. 

A  positive,  negative  and  zero  sequence  cur­

rent 

filter  is  used  to  obtain  a  single-phase 

voltage 

from  the 

three-phase 

line  currents, 

and  this  voltage  is  utilized  to  energize  fault 

detectors  and  to 

control  the  transmission  of 

alternate 

half  cycle 

blocks 

at  the 

power 

frequency

of  carrier  energy  from  both  ends  of 

the  line  section. 

The  carrier  signal  from  each  end  is  received 

at  the 

opposite 

end  of  the 

line  where  it  is 

rectified, 

and 

compared  with  the  phase  po­

sition 

of  the 

output 

voltage 

of  the  local 

sequence  filter. 

This  compRrison  takes 

place 

in  the  grid  circuit  of  a 

vacu�m  tube  which  is 

NEW  INFORMATION 

so  biased 

that  no  plate 

current 

flows 

when 

there 

is  no  filter  or  carrier 

voltage  on  its 

control  grid. 

The  polarity  of  the  filter  and 

carrier  voltages  is  such  that  no  current  flows 

in  the  vacuum  tube  plate  circuit  for  a  fault 

external 

to  the 

protected  line 

section  when 

the  line  �urrents 

are  exactly  in  phase  at  the 

two  ends. 

For  an  internal  fault  with  the  cur­

rents  at  the  two  ends  or  the  line 

180° 

out-of­

phase,  plate 

current  will  flow 

on  alternate 

half-cycles 

of 

the 

line 

current  frequency. 

This  plate  current  flows  through  a  transformer 

primary  winding,  and  the  a-c  voltage  developed 

on  the 

secondary 

side 

is  rectified 

and 

supplied  to  a  relay  whose 

contact  is  in  the 

trip  circuit. 

The  voltage  in  the  transformer 

secondary  is  sufficient  to  trip 

the  relay  for 

an  internal  fault. 

This  arrangement  thus  pro­

vides  simultaneous  tripping 

over  the  entire 

line  section  for  all 

faults  within  the  set­

tings 

of  the  relay. 

As  this  system  operates 

on 

line  current  only,  it  is  not  sub

j

ect  to 

tripping  on  power  swing 

or  out-of-synchronism 

conditions  since 

the 

circulating 

currents 

appear  to  the  relays  as  "·n  external  fault. 

If 

tripping  is  desired  on  an  out-of-synchronism 

condition,  auxiliary 

relays  must  be  added  for 

this  purpose. 

For  an  internal  fault  on  a  line 

fed  from  one  end  only,  tripping  will  occur 

at 

the 

terminal 

through  which 

fault  current  is 

flowing  into  the  line  section. 

COMPONENTS  OF  COMPLETE 

EQUIPMENT 

An  outline 

of  the  equipment 

used  at  each 

terminal 

of  a  transmission  line  section  is  as 

follows: 

l. 

One  type 

HKB 

relay  which 

includes  the 

sequence  filter, 

fault  detectors 

to 

start  the  transmlssion  of 

carrier 

and 

control  the  operating  element 

(

tripping 

EFFECTIVE  7-47 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Содержание HKB Series

Страница 1: ...es place in the grid circuit of a vacu m tube which is NEW INFORMATION so biased that no plate current flows when there is no filter or carrier voltage on its control grid The polarity of the filter a...

Страница 2: ...should trip the breaker 3 A coupling capacitor with carrier aux 4 iliary for introducing the carrier fre quency on to the transmission line This may be supplied with a potential device for obtaining...

Страница 3: ...FD2 is set to trip 25 ercent above tap value and supervises the operation of the tripping relay element R through the relay tube This tripping of the line breaker cannot occur until FDl and FD2 have...

Страница 4: ...age drop Eo across 4 R RELAY CURRENT 20 180 Fig 3 Typical Overall Characteristics of the Type HKB System R c of Figure 1 It is called operating volt age as it makes the grid of the relay tube positive...

Страница 5: ...tivity the relay R can be set to operate when the angle between the currents at the two ends of the line becomes any desired value such as 35 degrees as shown The preceding explanation is based on sin...

Страница 6: ...nnel can be used for other func tions such as telemetering load communication supervisory control tripping Fore these functions lead from the oscillator plate control and remote a separate circuit is...

Страница 7: ...laying equipment This can be done by plugging a hand set at the carrier set at the relay switchboard or rrom a desk set permanently wired to the equipment The push to talk type or communication is emp...

Страница 8: ...WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Отзывы: