background image

J.L.  41-610.1  c 

INSTALLATION 

• 

OPERATION 

• 

MAINTENANCE 

INSTRUCTIONS 

TYPE  HQS  PHASE  SELECTOR  RELAY  FOR 

SELECTIVE-POLE  CARRIER  RELAYING 

CAUTION 

Before  putting  ·relays  into  service, 

remove  all  blocking  which  may  have  been  in­
serted  for  the  purpose  of  securing  the  parts 
during 

shipment, 

make  sure  that  all  moving 

parts  operate  freely,  inspect  the  contacts  to 
see  that  they  are  clean  and  close  properly, 
and  operate  the  relay  to  check  the  settings 
and  electrical  connections. 

APPLICATION 

The  type  HQS  relay  operates  on  negative  and 

zero 

sequence 

currents  to  select  the  faulted 

phase 
occurs 

when 

on 

the 

single  phase-to-ground  fault 

protected  transmission  line. 

The  zero  sequence  current  is  obtained  from  the 

neutral 

of  the  line  current  transformers,  and 

the  negative  sequence  current  from  an  external 
three-phase  filter  supplied  with  the  relay. 

CONSTRUCTION  AND  OPERATION 

The  type  HQS  relay  consists  of  three  phase 

selector  elements, 

three  contactor  switches, 

and  three  operation  indicators  mourited  in  the 

standard 

case  of  Figure  4.  The 

external 

three-phase 

negative, 

sequence 

filter  is 

mounted  in  the  case  of  Figure 

3. 

The  oper­

at·ion  of  this  relay  in  the  carrier  scheme  is 

described  in  I.L.  41-600.2. 

Phase  Selector 

The  phase  selector  element  is  similar  to  the 

H  directional  element  as  used  in  the  type 

HZ 

and  HRK-P  relays. 

The  primary  of  a  small  cur­

rent  transformer  receives  the  zero  sequence 

_component  of  line  current  which  causes  a  large 

current  to  flow  in  a  one-turn  movable  aluminum 

secondary. 

Two  other  current 

coils  are 

mounted  on  either  side  of  a  magnetic  frame  and 
these  coils  receive  the  negative  sequence  com­
ponent 

of 

line  current  from  an  external 

SUPERSEDES  I.L.  41-610.1 B 

filter. 

These  zero  and  negative  sequence 

elements  are  assembled  at  right  angle  to  each 
other  with  the  one-turn  loop  in  the  air  gaps 
of  the  negative  sequence  current  coil  flux 
path. 

The  interaction  of  the  two  fluxes  pro­

duces  torque  and  rotates  the  loop  in  a  direc­
tion  depending  on  the  relative  instantaneous 
direction  of  current  flow  in  the  two  coils. 

An 

Isolantite  arm  extends  from  the  moving 

loop  and  supports  a  rectangular  silver  contact 

which  bridges  two  stationary  contacts  mounted 
on  either  side  of  the  loop.  The  stationary 
contacts 
on  the 

are 
lower 

silver  conical  surfaces  mounted 

end  of  vertically 

hanging 

springs.  The  contact  separation  is  adjustable 
by  a  small  screw  near  the  upper  end  of  the 
rigid 

stationary  contact  supporting  arm. 

One 

of  these  supporting  arms  hangs  parallel  to 
each  of  the  four  stationary  contacts. 

The  set 

screw  on  the  lower  end  of  this  arm  provides 
the  contact  follow  adjustment. 

Two  additional 

screws  on  the  movement  frame  beneath 

the 

negative  sequence  coil  iron  limit  the  movement 

of  the  loop. 

There  are  three  of  these  phase 

selector  elements, 

one  for  each  of  the  three 

phases  and  designated  SA,  SB  and 

s0 

for  phases 

A,  B,  and  C  respectively.  The  sub  numbers 

and 

indicate  the  negative  and  zero  sequence 

coils. 

Contactor  Switch 

The  d-e.  contactor  switch  in  the  relay  is  a 

small  solenoid  type  switch. 

A  cylindrical 

plunger  with  a  silver  disc  mounted  on  its 
lower  end  moves  in  the  core  of  the  solenoid. 
As  the  plunger  travels  upward, 

the 

disc 

bridges  three  silver  stationary  contacts. 

The 

coil  is  in  series  with  the  main  contacts  of 
the  relay  and  with  the  trip  coil  of  the 
breaker. 

When  the  relay  contacts  close,  the 

coil  becomes  energized  and  closes  the  switch 

EFFECTIVE  FEBRUARY  1949 

www 

. ElectricalPartManuals 

. com 

Содержание HQS

Страница 1: ...ine current from an external SUPERSEDES I L 41 610 1B filter These zero and negative sequence elements are assembled at right angle to each other with the one turn loop in the air gaps of the negative...

Страница 2: ...of the filter is beyond the scope of this leaflet and is covered in catalog section 41 287 on the type CRS relay CHARACTERISnCS The type HQS relay js an auxiliary relay used in the carrier relaying sc...

Страница 3: ...remaining switches The order of opening the remaining switches is not opening the test switches important In they should be moved all the way back against the stops With all the switches fully opened...

Страница 4: ...ull open position 4 the ten circuit test plug can be inserted in the contact jaws This connects the relay elements to a set of binding posts and com pletely isolates the relay circuits from the extern...

Страница 5: ...the right and bridge sc the stationary contacts Reverse the connections to terminals 25 and 26 The left hand con tacts should now remain firmly closed Raise the current to 15 amperes and make sure tha...

Страница 6: ...relay terminals 19 21 and 23 to 14 l I I gether With balanced three phase currents of 5 amperes 60 cycles phase rotation A B C applied to the filter input terminals A B C and the neutral made by conn...

Страница 7: ...6 1 o l c 0 PANEL LOCIITION fOil PROJECTION TYPE KTQ 0 I I I PANEL LOCATION I Oit seMI F USII TVPE MTGo t l8 HTG STUD 2 Ri O Fig 4 0utline and Drilling Plan of the M20 Projection or Semi Flush Type F...

Страница 8: ...WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Отзывы: