background image

TYPE  HQS  RELAY 

.lc 

and  the  filter  are 

shown  in  the 

Carrier 

Current  Schematic  for  selective  pole  tripping 
supplied  with  each  terminal. 

ADJUSTMENTS  AND  MAINTENANCE 

The  proper  adjustments  to  insure  correct 

operation  of  this  relay  have  been  made  at  the 

factory  and  should  not  be  disturbed  after  re­

ceipt  by  the  customer. 

If  the  adjustments 

have  been  changed,  the  relay  taken  apart  for 
repairs,  or  if  it  is 

desired  to  check  the 

adjustments 

at  regular  maintenance  periods, 

the  instructions  below  should  be  followed. 

All  contacts  should  be  periodically  cleaned 

with  a  fine  file.  S#l002110  file  is  recom­
mended  for  this  purpose.  The  use  of  abrasive 

material  for  cleaning  contacts  is  not  recom­
mended, 

because  of  the  danger  of  embedding 

small  particles  in  the  face  of  the  soft  silver 
and  thus  impairing  the  contact. 

Phase  Selector  Element 

Check  the  free  movement  of  each  element  with 

the  relay  in  a  vertical  position  to  see  that 

it 

is  free  from  friction  and  properly  center­

ed. 

The 

loop  should  assume  a  vertical  po­

sition  with  the  contacts  open  when  the  element 
is  completely  deenergized. 

With  the  loop  in  the  neutral  position  de­

termined 

by 

gravity, 

adjust  both  left-hand 

stationary  contacts  (front  view)  so  that  there 
is  contact  gap  of  .01011  between  moving  contact 

bridge  and  the  stationary  contacts. 

Adjust 

the  left  hand  back  stop  screws  for  .01011 

con­

tact  deflection.  Adjust  the  left  stop  which 
strikes  against  the  loop  so  that  it  makes  con­
tact  against  the  loop  at  the  same  time  the 

moving  contact  deflects  the  stationary  contact 
against  the  two  back  screws. 

Repeat  these  ad­

justments  for  the  right  hand  contacts 

and 

stops. 

Connect  terminals  25  and  24  together  and 

pass  1  ampere,  60  cycles,  from  terminals  26  to 

23. 

(This  test  is  without  the  filter). 

The 

moving 

should 

contact  of  the  bottom 

element 

move  to  the  right  and  bridge 

(sc) 

the 

stationary  contacts. 

Reverse  the  connections 

to  terminals  25 

and  26.  The  left-hand  con­

tacts 

should  now  remain  firmly  closed.  Raise 

the 

current  to  15  amperes  and  make  sure 

that 

the 

loop  stop  screws  have  the  adjustment  for 

minimum 

contact  vibration. 

This 

current 

should 

be 

passed  only  momentarily  to  prevent 

overheating  the  fault  detector  coils. 

Repeat  the  tests  on  the  middle  element  (SB) 

by  connecting  terminals  22  and  25  together  and 

passing  current  through  terminals  21  and  26 
and  on  the  top  element 

(SA)  by  connecting 

terminals  25  and  22  together  and  passing  cur­
rent  through  terminals  19  and  26. 

Adjust  the  bearing  screws  of  the  moving  loop 

so  that  there  is  about  .010  inch  end  play. 
See  that  the  loop  does  not  bind  or  strike 
against  the  iron  or  coil  when  pressed  against 

either  end  jewel. 

Contactor  Switch 

Adjust  the 

a  clearance 
the 

moving 

picked  up. 

stationary  c·ore  of  the  switch  for 

between  the  stationary  core  and 

core  of  1/64"  when  the  switch  is 
This  can  be  done  by  turning  the 

relay  up-side-down  or  by  disconnecting 

the 

switch  and  turning  it  up-side-down. 

Then 

screw  up  the  core  screw  until  the  moving  core 
starts  rotating.  Now,  back  off  the  core  screw 
until  the  moving  core  stops  rotating.  This 
indicates  the  points  where  the  play  in  the 
assembly  is  taken  up, 

and  where  the  moving 

core  just  separates  from  the  stationary  core 
screw. 

Back  off  the  core  screw  approximately 

one  turn  and  lock  in  place.  This  prevents  the 

moving  core  from  striking  and  sticking  to  the 
stationary  core  because  of  residual  magnetism. 

Adjust  the  contact  clearance  for  3/32" 

by 

means 

of  the  two  small  nuts  on  either  side  of 

the 

Micarta  disc. 

The  switch  should  pick  up 

at  4  amperes  d-e. 

Test  for  sticking  after  30 

amperes  d-e  have  been  passed  through  the  coil. 

The  coil  resistance  is  approximately  .025  ohms. 

Operation  Indicator 

Adjust  the  indicator  to  operate  at  1.0 

ampere  d-e.  gradually  applied  by  loosening  the 
two  screws  on  the  under  side  of  the  assembly, 

and  moving  the  bracket  forward  or  backward. 

www 

. ElectricalPartManuals 

. com 

Содержание HQS

Страница 1: ...ine current from an external SUPERSEDES I L 41 610 1B filter These zero and negative sequence elements are assembled at right angle to each other with the one turn loop in the air gaps of the negative...

Страница 2: ...of the filter is beyond the scope of this leaflet and is covered in catalog section 41 287 on the type CRS relay CHARACTERISnCS The type HQS relay js an auxiliary relay used in the carrier relaying sc...

Страница 3: ...remaining switches The order of opening the remaining switches is not opening the test switches important In they should be moved all the way back against the stops With all the switches fully opened...

Страница 4: ...ull open position 4 the ten circuit test plug can be inserted in the contact jaws This connects the relay elements to a set of binding posts and com pletely isolates the relay circuits from the extern...

Страница 5: ...the right and bridge sc the stationary contacts Reverse the connections to terminals 25 and 26 The left hand con tacts should now remain firmly closed Raise the current to 15 amperes and make sure tha...

Страница 6: ...relay terminals 19 21 and 23 to 14 l I I gether With balanced three phase currents of 5 amperes 60 cycles phase rotation A B C applied to the filter input terminals A B C and the neutral made by conn...

Страница 7: ...6 1 o l c 0 PANEL LOCIITION fOil PROJECTION TYPE KTQ 0 I I I PANEL LOCATION I Oit seMI F USII TVPE MTGo t l8 HTG STUD 2 Ri O Fig 4 0utline and Drilling Plan of the M20 Projection or Semi Flush Type F...

Страница 8: ...WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Отзывы: