TYPE  HQS  RELAY 

If 

the  two  helical  springs  which  reset  the 

aramture  are  replaced  by  new  springs,  they 
should  be 

weakened  slightly  to  stretching  to 

obtain  the  1 

ampere  calibration.  The  coil 

resistance  is  approximately  0.16  ohm. 

Three  - Phase  Negative  Sequence  Filter 

The  filter  is  adjusted  for  balance  at  the 

factory  and  no  further  adjustments  or  mainte­
nance  should  be  required.  With  balanced  three 
phase  currents  of  10  amperes,  60  cycles,  phase 

rotation  A, 

B, 

C,  introduced  into  the  input 

terminals  as  marked  on  Fig.  2,  the  voltage  be­
tween  the  output 

terminals  A',  B', 

and  C', 

should  be  zero.  Use  a  high  resistance  volt­

meter  for  this  chec;,. 

Connect 

terminals  A', 

B', 

and  C'  to  termi­

nals  20, 

22  and  24  of 

the  type  HQS  relay. 

Connect  the  relay  terminals  19,  21  and  23  to-

14/l 

gether, 

With  balanced  three-phase  currents  of 

amperes,  60  cycles,  phase  rotation  A,  B,  C, 

applied  to  the  filter  input  terminals  A,  B,  C, 
and  the 

neutral  made  by  connecting  terminals 

A", 

B" 

and  C" 

together, 

the  voltage  across 

tke  relay  terminals  19  and  20,  21  and  22,  and 
23  and  24  should  be 

zero. 

Now,  reverse  the 

connections  to  the  filter  input  terminals  A 

and  B  and  check  the  voltage  now  appearing 

across  the  relay  terminals. 

These  three  volt­

ages  should  be  substantially  0.7  volt. 

RENEWAL  PARTS 

Repair  work  can  be  done  most  satisfactorily 

at 

the  factory. 

However, 

interchangeable 

parts  can  be 

furnished  to  the  customers  who 

are 

equipped  for  doing 

repair  work. 

When 

ordering  parts,  always  give  the  complete  name­
plate  data. 

.leJ0-.32  -!>CREW.S 

FOR  TERMIAIAW 

if 

D/.11,  MT4. HOLES 

(4-HOLES) 

Fig. 3-0utline and Drilling Plan of the Three Phase Negative  Sequence  Filter. 

www 

. ElectricalPartManuals 

. com 

Содержание HQS

Страница 1: ...ine current from an external SUPERSEDES I L 41 610 1B filter These zero and negative sequence elements are assembled at right angle to each other with the one turn loop in the air gaps of the negative...

Страница 2: ...of the filter is beyond the scope of this leaflet and is covered in catalog section 41 287 on the type CRS relay CHARACTERISnCS The type HQS relay js an auxiliary relay used in the carrier relaying sc...

Страница 3: ...remaining switches The order of opening the remaining switches is not opening the test switches important In they should be moved all the way back against the stops With all the switches fully opened...

Страница 4: ...ull open position 4 the ten circuit test plug can be inserted in the contact jaws This connects the relay elements to a set of binding posts and com pletely isolates the relay circuits from the extern...

Страница 5: ...the right and bridge sc the stationary contacts Reverse the connections to terminals 25 and 26 The left hand con tacts should now remain firmly closed Raise the current to 15 amperes and make sure tha...

Страница 6: ...relay terminals 19 21 and 23 to 14 l I I gether With balanced three phase currents of 5 amperes 60 cycles phase rotation A B C applied to the filter input terminals A B C and the neutral made by conn...

Страница 7: ...6 1 o l c 0 PANEL LOCIITION fOil PROJECTION TYPE KTQ 0 I I I PANEL LOCATION I Oit seMI F USII TVPE MTGo t l8 HTG STUD 2 Ri O Fig 4 0utline and Drilling Plan of the M20 Projection or Semi Flush Type F...

Страница 8: ...WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Отзывы: