5.11 S: Elevator Parameters
■ S5-01: Short Floor Operation Selection
Enables and disables the Short Floor function.
Note: 1. The Short Floor and Advanced Short Floor functions cannot be used during Rescue Operation.
2. Do not use Short Floor or Advanced Short Floor w hen the analog input term inals are configured to supply the speed reference.
3. The drive will accelerate or decelerate to the specified speed reference at the specified A ccel/Decel rate i f the speed priority is set for
multi-step speed reference (d1-18 = 0 or 3) and the leveling speed reference is selected during Short Floor or A dvanced Short Floor.
No.
Parameter Name
Setting Range
Default
S5-01
Short Floor Operation Selection
0 to 2
0
0: Disabled
1: Enabled (Short Floor Operation)
2: Enabled (Advanced Short Floor Operation)
■ S5-02: Nominal Speed for Short Floor Calculation
Determines the rated speed used to calculate the distance for the Short Floor function when speed priority is set for
Multi-step Speed Reference (d1-18 = 0 or 3).
No.
Parameter Name
Setting Range
Default
S5-02
Nom inal Speed for Short Floor Calculation
0.0 to 100.0%
0.0%
■ S5-03: Short Floor Minimum Constant Speed Time
Sets the minimum time o f the constant speed operation when the Advanced Short Floor function is enabled (S5-01 = 2).
No.
Parameter Name
Setting Range
Default
S5-03
Short Floor Minimum Constant Speed Time
0 to 2.0 s
0.0 s
■ S5-04: Distance Calculation Acceleration Time Gain
Sets the gain used to adjust the jerk at acceleration for an optimum speed calculation when Short Floor Operation
Selection (S5-01) is set to 2.
• Increase the gain level set to S5-04 and S5-05 if the leveling time is too short or if the optimum speed calculated by the
drive is too fast.
• Decrease the gain level set to S5-04 and S5-05 if the leveling time is too long or if the optimum speed calculated by the
drive is too slow.
No.
Parameter Name
Setting Range
Default
S5-04
Distance Calculation Acceleration Time Gain
50.0 to 200.0%
150.0%
Note: Setting S5-04 too low may trigger an overrun due to faster optimum speeds and shortened leveling times. Avoid setting this gain
less than 100%.
■ S5-05: Distance Calculation Deceleration Time Gain
Sets the gain used to adjust the jerk at deceleration and optimum speed calculation when Short Floor Operation Selection
(S5-01) is set to 2.
• Increase the gain level set to S5-04 and S5-05 if the leveling time is too short or if the optimum speed calculated by the
drive is too fast.
• Decrease the gain level set to S5-04 and S5-05 if the leveling time is too long or if the optimum speed calculated by
the drive is too slow.
No.
Parameter Name
Setting Range
Default
S5-05
Distance Calculation Deceleration Time Gain
50.0 to 200.0%
150.0%
Note: Setting S5-05 too low may trigger an overrun due to faster optimum speeds and shortened leveling times. Avoid setting this gain
less than 100%.