B.3 Parameter Table
No. (Addr.)
T2-08
(734H)
Name
Description
Number o f Motor Poles
Enter the number o f motor poles for the motor as indicated on the motor nameplate.
Setting
Page
Default: 6
Min: 2
Max: 48
104
Default: 150 r/min
Min: 0 r/min
Max: 24000 r/min
104
Default: -
Min: 0.000 Q
Max: 65.000 Q
104
Default: -
Min: 0.00 mH
Max: 600.00 mH
104
Default: -
Min: 0.00 mH
Max: 600.00 mH
104
Default: 1
Min: 0
Max: 1
104
Default: -
Min: 0.0
Max: 6500.0 <30>
104
Default: 1024 ppr
Min: 1 ppr
Max: 15000 ppr
104
Default: 0.0 deg
Min: -180.0 deg
Max: 180.0 deg
104
T2-09
(731H)
Motor Base Speed
Enter the base speed for the motor as indicated on the motor nameplate.
T2-10
(754H)
Single Phase Stator Resistance
Enter the 1-phase resistance o f the stator winding.
T2-11
(735H)
Motor d-Axis Inductance
Enter the d-axis inductance for the motor as indicated on the motor nameplate.
T2-12
(736H)
Motor q-Axis Inductance
Enter the q-axis inductance for the motor as indicated on the motor nameplate.
T2-13
(755H)
Induced Voltage Constant Unit
Selection
0: mV/(r/min). E 5-09 w ill automatically be set to 0.0, and E 5-24 w ill be used.
1: mV/(rad/sec). E 5-24 w ill automatically be set to 0.0, and E5-09 w ill be used
T2-14
(737H)
Motor Induced Voltage Constant
Enter the induced voltage coefficient for the motor as indicated on the motor nameplate.
T2-16
(738H)
Encoder Resolution
Sets the number o f pulses per revolution for the PG being used (pulse generator or encoder).
T2-17
(757H)
Encoder Offset
Sets the offset between encoder offset and the rotor magnetic axis.
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
<4> D efault setting value varies by the drive model (o2-04).
<9> Values shown here are for 200 V class drives. Double the value w hen using a 400 V class drive.
<10> The display resolution depends on the rated output power o f the drive. M odels CIM R-LC2A0018 to 2A0033 and CIM R-LC4A0009 to
4A 0018 display values in 0.01 A units, w hile models CIM R-LC2A0047 to 2A0415 and CIM R-LC4A0024 to 4A 0216 display values in 0.1 A
units.
<30> Setting units are determined by the induced voltage constant unit selection for PM motors set to T2-13.
♦ U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
■ U1: Operation Status Monitors
No. (Addr.)
Name
Description
Analog Output
Level
Unit
Page
U1-01
(40H)
Speed Reference
Monitors the speed reference.
10 V: M ax frequency
0.01%
<31>
U1-02
(41H)
Output Speed
D isplays the output speed.
10 V: M ax frequency
0.01%
<31>
U1-03
(42H)
Output Current
D isplays the output current.
10 V: D rive rated
current
U 1-04
(43H)
Control Method
V /f Control
Open Loop Vector Control
Closed Loop Vector Control
Closed Loop Vector Control for PM
N o signal output
available
U1-05
(44H)
Speed Feedback
CLV
■
CLV/PM
D isplays the motor speed feedback.
10 V: M ax Frequency
0.01%
<31>
U1-06
(45H)
Output Voltage Reference
D isplays the output voltage.
10 V: 200 Vrms <9>
U 1-07
(46H)
DC Bus Voltage
D isplays the DC bus voltage.
10 V: 400 V <9>
1 Vdc
U1-08
(47H)
Output Power
D isplays the output power (this value is calculated internally).
10 V: Drive rated
power (kW)
U1-09
(48H)
Torque Reference
CLV
■
CLV/PM
Monitors the internal torque reference.
10 V: Motor rated
torque
0.1%
<10>
V/f
<12>
V/f
IE