1.2 General Description
1.2
General Description
♦ L1000A Model Overview
Motor Power
3-Phase 200 V Class
3-Phase 400 V Class
kW (HP)
Model CIMR-LC
Rated Output Current (A)
Model CIMR-LC
Rated Output Current (A)
4.0
2A0018
17.5 <1>
4 A 0009
9.2 <1>
5.5
2A0025
25 <1>
4A 0015
14.8 <1>
7.5
2A0033
33 <1>
4A 0018
18 <1>
11
2A 0047
4 7 <1>
4A 0024
24 <1>
15
2A 0060
60 <1>
4A0031
31 <1>
18.5
2A0075
75 <1>
4A 0039
39 <1>
22
2A0085
85 <1>
4A 0045
45 <1>
30
2A0115
115 <1>
4A 0060
60 <1>
37
2A0145
145 <2>
4A 0075
75 <1>
45
2A0180
180 <2>
4A0091
91 <1>
55
2A0215
215 <2>
4A 0112
112 <2>
75
2A0283
283 <2>
4A 0150
150 <2>
90
2 A 0346
346 <2>
4A 0180
180 <2>
110
2A0415
415 <2>
4A 0216
216 <2>
<1> These values assume the carrier frequency is not set higher than 8 kHz.
<2> These values assume the carrier frequency is not set higher than 5 kHz.
Note: The drive autom atically decreases the rated output current when setting higher carrier frequency.
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual