5.7 H: Terminal Functions
Setting 5C: Stop Distance Correction
When this terminal closes and a direct landing is selected for the stopping method (S5-10 = 1), the drive will stop at the
designated floor with greater accuracy.
Refer to Stop Distance on page 353
for details.
Setting 67: Communication test mode
The drive has a built-in function for self-diagnosing serial communications operation. The test involves wiring the send
and receive terminals o f the RS-485/422 port together. The drive transmits data and then confirms that the
communications are received normally. Refer to
Self-Diagnostics on page 393
for details on how to use this function.
Setting 79: Brake feedback
This input allows the drive to monitor the brake operation and issue a fault if the brake status does not match the brake
command (digital output set to И 2-П П = 50).
♦ H2: Multi-Function Digital Outputs
■ H2-01 to H2-05: Terminals M1-M2, M3-M4, M5-M6, P1-PC, and P1-P2 Function Selection
The drive has three multi-function output terminals.
Table 5.12
lists the functions available for these terminals using H2-
01 through H2-05.
No.
Parameter Name
Setting Range
Default
H2-01
Terminals M 1-M 2 Function Selection
0 to 161
50: Brake control
H2-02
Terminals M 3-M 4 Function Selection
0 to 161
51: Output control contactor
H2-03
Terminals M 5-M 6 Function Selection
0 to 161
6: Drive ready
H 2-04
Terminals P1-C1 Function Selection (photocoupler)
0 to 161
37: During frequency output
H2-05
Terminals P2-C2 Function Selection (photocoupler)
0 to 161
F : Through Mode
Table 5.12 Multi-Function Digital Output Terminal Settings
Setting
Function
Page
Setting
Function
Page
0
During Run
175
1B
During Baseblock 2 (N .C.)
181
Zero Speed
1 76
1C
Motor 2 Selection
181
2
Speed Agree 1
1 76
1D
During Regeneration
181
3
U ser-set Speed Agree 1
1 76
1E
Restart Enabled
181
4
Speed Detection 1
1 7 7
1F
Motor Overload Alarm (oL1)
181
5
Speed Detection 2
1 7 7
20
Drive Overheat Pre-alarm (oH)
181
6
Drive Ready
178
2F
Maintenance Period
181
7
D C Bus Undervoltage
178
30
During Torque Limit
182
8
During Baseblock (N.O.)
178
33
Within Position Lock Bandwidth
182
9
Speed Reference Source
178
37
During Frequency Output
182
A
U p/Dow n Command Source
178
50
Brake Control
182
B
Torque Detection 1
178
47
Input Phase Loss
182
E
Fault
178
4E
Braking Transistor Fault (rr)
182
F
N ot used (Through M ode)
179
51
Output Contactor Control
182
10
Minor Fault
179
52
Door Zone Reached
182
11
Fault Reset Command A ctive
179
53
N ot Zero Speed
182
12
Timer Output
179
54
Light Load Direction
182
13
Speed Agree 2
179
55
Light Load Direction Detection Status
182
14
U ser-set Speed Agree 2
179
58
Safe D isable Status
183
15
Speed Detection 3
180
60
Internal Cooling Fan Alarm
183
16
Speed Detection 4
180
61
Motor Pole Search Status
183
18
Torque Detection 2
178
100 to 161
Functions 0 to 61 with Inverse Output
183
1A
During Reverse
181
-
-
-
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Description
Open
Drive is stopped.
Closed
A n U p/Dow n command is input or the drive is during deceleration or during DC injection.
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual