5.9 n: Special Adjustments
■ n8-81: High Frequency Injection during Rescue Operation
Sets the frequency used for High Frequency Injection during Rescue Operation.
No.
Name
Setting Range
Default
n8-81
High Frequency Injection during R escue Operation
25 to 1000 Hz
90 Hz
■ n8-82: High Frequency Injection Amplitude during Rescue Operation
Sets the amplitude for High Frequency Injection during Rescue Operation as a percentage o f the voltage (200 V or 400
V).
No.
Name
Setting Range
Default
n8-82
High Frequency Injection Amplitude during R escue Operation
0.1 to 99.9%
15.0%
■ n8-84: Polarity Detection Current
Sets the current level (E5-03) as a percentage for detecting polarity during Initial Polarity Estimation.
No.
Name
Setting Range
Default
n8-84
Polarity Detection Current
0 to 150%
100%
■ n8-86: Magnet Pole Search Error Detection Selection
Enables fault detection for Initial Polarity Estimation (dv8).
No.
Name
Setting Range
Default
n8-86
Magnet Pole Search Error Detection Selection
0 or 1
0
0: Disabled
After searching for the rotor pole position one time, the drive starts using the detected rotor position. If the detected
position is wrong, an error occurs when the drive attempts to run the motor. The initial pole search takes approximately
1.5 s.
1: Enabled
The rotor pole position search is executed multiple times. The drive starts using the detected rotor position only if there is
no difference between the search results. Otherwise a dv8 error will be output. The initial pole search takes
approximately 1.5 to 5.0 s.
■ Other Settings
Parameters n8-29 to n8-33 can be used to adjust the current control loop. Adjustment is not normally required.
Parameter n8-62 sets a voltage limit in order to prevent voltage saturation.
■ n8-29: q-Axis Current Control Gain during Normal Operation
Sets the q-Axis proportional gain for the automatic current regulator.
No.
Name
Setting Range
Default
n8-29
q-Axis Current Control Gain during Normal Operation
0 to 2000 rad/s
1000 rad/s
■ n8-30: q-Axis Current Control Integral Time during Normal Operation
Sets the q-Axis integral time for the automatic current regulator.
No.
Name
Setting Range
Default
n8-30
q-Axis Current Control Integral Time during Normal Operation
0.0 to 100.0 ms
10.0 ms
■ n8-32: d-Axis Current Control Gain during Normal Operation
Sets the d-Axis proportional gain for the automatic current regulator.
No.
Name
Setting Range
Default
n8-32
d-Axis Current Control Gain during Normal Operation
0 to 2000 rad/s
1000 rad/s
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual