5.6 F: Option Settings
■ F1-04, F1-10, F1-11: Operation at Speed Deviation (dEv), Detection Level, Delay Time
A speed deviation error (dEv) is triggered when the difference between the speed reference and the speed feedback
exceeds the value set in F1-10 for longer than the time set in F1-11. The stopping method when a speed deviation fault
occurs can be selected in parameter F1-04.
No.
Parameter Name
Setting Range
Default
F1-04
Operation Selection at Deviation
0 to 3
3
F1-10
E xcessive Speed Deviation Detection Level
0 to 50%
10%
F1-11
E xcessive Speed Deviation Detection D elay Time
0.0 to 10.0 s
0.5 s
Settings fo r Param eter F1-04:
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only (drive continues operating while “dEv” flashes on the screen)
■ F1-05: Encoder 1 Rotation Direction Selection
Determines the direction indicated by the motor encoder signal.
Refer to
PG Encoder Setup on page 91
for details on how to set the direction for the encoder and the motor.
No.
Parameter Name
Setting Range
Default
F1-05
Encoder 1 Rotation Direction Selection
0 or 1
0
<1>
<1> D eterm ined by the control mode: 0 when A1-02 = 3, 1 w hen A1-02 = 7.
Setting 0: Phase A leads phase B with an Up command.
Setting 1: Phase B leads phase A with an Up command.
■ F1-06: PG1 Pulse Monitor Output Division Ratio
Sets the ratio between the pulse input and the pulse output o f a speed feedback option card as a three digit number, where
the first digit (n) sets the numerator and the second and third digit (m) set the denominator as shown below:
(1 + n)
P u ls e In p u t
P u ls e O u tp u t
m
Example: To have a ratio of 1/32 between the speed feedback option card pulse input and output, set F1-06 = 032.
No.
Parameter Name
Setting Range
Default
F1-06
PG1 Pulse Monitor Output D ivision Ratio
1 to 132 (1 to 1 - )
32
1
■ F1-18: dv3 Detection Selection (CLV/PM)
Sets the number o f times the drive will detect a dv3 situation before triggering a dv3 fault. The drive detects a dv3
condition when the torque reference and speed reference are in opposite directions while the difference between the
actual motor speed and the speed reference is greater than 30%. Setting F1-18 to 0 disables dv3 detection.
No.
Parameter Name
Setting Range
Default
F1-18
dv3 Detection Selection
0 to 10
10
Note: A comm on cause for a dv3 fault is the incorrect setting o f E5-11. M ake sure the correct encoder offset has been entered to E5-11.
■ F1-19: dv4 Detection Selection (CLV/PM)
Sets the number o f pulses necessary to trigger a dv4 fault when there is a motor speed deviation opposite to the frequency
reference. Setting F1-19 to 0 disables dv4 detection.
No.
Parameter Name
Setting Range
Default
F1-19
dv4 Detection Selection
0 to 5000
128
N o te :
A comm on cause for a dv4 fault is the incorrect setting o f E5-11. M ake sure the correct encoder offset is set to E5-11.
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual