5.7 H: Terminal Functions
Setting F: Not used (Through mode)
Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function
in the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or
MEMOBUS/Modbus communications.
Setting 10: Minor fault
Output closes when a minor fault condition is present.
Setting 11: Fault reset command active
Output closes whenever there is an attempt to reset a fault situation from the control circuit terminals, via serial
communications, or using a communications option card.
Setting 12: Tim er output
This setting configures a digital output terminal as output for the timer function. Refer to
b4: Delay Timers on page 142
for details.
Setting 13: Speed agree 2 (fref /fout agree 2)
Closes whenever the actual output speed or motor speed (CLV, CLV/PM) is within the speed agree width (L4-04) o f the
current speed reference, regardless o f the direction.
Status
Description
Open
Output speed or motor speed does not match the speed reference w hile the drive is running.
Closed
Output speed or motor speed is within the range o f speed reference ±L4-04.
Note: D etection w orks in both forward and reverse.
Refer to
L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 193
for more details.
Setting 14: User-set speed agree 2 (fref /fset agree 2)
Closes whenever the actual output speed or motor speed (CLV, CLV/PM) and the speed reference are within the speed
agree width (L4-04) o f the programmed speed agree level (L4-03). As the detection level L4-03 is a signed value.
detection works in the specified direction only.
Status
Description
Open
Output speed or motor speed and speed reference are both outside the range o f L4-03 ±L 4-04
Closed
Output speed or motor speed and the speed reference are both with in the range o f L4-03 ±L4-04
Output speed
User Set
Speed Agree 2
OFF
ON
F ig u r e 5 .2 4 U s e r S e t S p e e d A g r e e 2 E x a m p le w ith a P o s i ti v e L 3-04 V a lu e
Refer to
L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 193
for more details.
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual