8.5 Installing Peripheral Devices
• Connecting a Noise Filter
■ Reducing Radiated, Conducted, and Induced Noise
Drives generate noise that can potentially affect surrounding devices like PLCs, etc.
•
Radiated Noise:
Electromagnetic waves noise throughout the radio bandwidth radiated from the drive and cables.
•
Conducted Noise:
Noise generated by the drive and emitted to through the power lines.
•
Induced Noise:
Noise generated by electromagnetic induction can affect control signal lines.
Take the following measurements to prevent noise causing malfunction o f other drives or devices:
• Install all components on a well grounded metal plate.
• Keep the motor cable as short as possible.
• Use noise filters on the input side o f the drive to reduce conducted noise.
• Install noise filters on the input and output side o f the drive, install the drive in a metal enclosure panel and use a
shielded motor cable to reduce radiated noise.
• Use shielded motor and control circuit lines and lay control circuit lines at least 30 cm away from power lines in order
to prevent malfunction due to induced noise.
A
c i
D
;
e
R / L 1
,U /T 1
G
I w
/ m
N
---- ---
_________
1
H
A - M etal e n c l o s u r e
B - P o w e r s u p p ly
C - In p u t n o is e filte r
D - D rive
E - O u tp u t n o is e filte r
F ig u r e 8.21 R e d u c in g R a d io F r e q u e n c y N o ise
J
F - S h ie ld e d m o to r c a b le
G - M otor
H - S e p a r a t e a t le a s t 3 0 cm
I - C o n t r o l s ig n a l lin e s
J - C o n tro lle r
■ Input-Side Noise Filter
Drive outputs generate noise as a result of high-speed switching. This noise flows from inside the drive back to the power
supply, possibly affecting other equipment. Installing a noise filter to the input side of the drive can reduce the amount of
noise flowing back into the power supply. This also prevents noise from entering the drive from the power supply.
• Use a noise filter specifically designed for AC drives.
• Install the noise filter as close as possible to the drive.
A - P o w e r s u p p l y
B - I n p u t- s id e n o is e filte r
C - D rive
D - O th e r c o n tr o l d e v ic e
F ig u r e 8 .2 2 In p u t-S id e N o is e F ilte r ( T h r e e - P h a s e 2 0 0 /4 0 0 V)
This drive is tested according to European standards IEC61800-5-1 and complies with the EMC guidelines. Refer to
EMC Guidelines Compliance on page 398
for details about EMC filter selection and installation.
T
F
V /T 2
B
C
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
309
P
e
ri
p
h
e
ra
l
D
e
v
ic
e
s
&
O
p
ti
o
n
s