6.3 Fault Detection
D i g i t a l O p e r a t o r D i s p l a y
F a u l t N a m e
CPF 03
CPF03
Control Board Connection Error
Connection error between the control board and the drive
C a u s e
P o s s i b l e S o l u t i o n
There is a connection error.
• Turn o ff the power and check the connection between the control board and the drive
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
Drive fails to operate properly due to noise interference.
• Check the various options available to m inim ize the effects o f noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• U se only recommended cables or other shielded line. Ground the shield on the controller side or on the drive input power side.
• Ensure that other equipment such as switches or relays do not cause noise and use surge absorbers if required.
• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive power supply input.
D i g i t a l O p e r a t o r D i s p l a y
F a u l t N a m e
[PFOB
CPF06
EEPROM Memory Data Error
A n error in the data saved to EEPROM
C a u s e
P o s s i b l e S o l u t i o n
There is an error in EEPROM control circuit.
• Turn o ff the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
The power supply was switched o ff w hile parameters
were being saved to the drive.
Reinitialize the drive (A1-03).
Power to the control board was lost w hile writing
parameter settings during R escue Operation.
Reinitialize the drive (A1-03).
D i g i t a l O p e r a t o r D i s p l a y
F a u l t N a m e
EPF 01
CPF07
Terminal Board Connection Error
CPF 00
CPF08
C a u s e
P o s s i b l e S o l u t i o n
There is a faulty connection between the terminal board
and control board.
• Turn o ff the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
D i g i t a l O p e r a t o r D i s p l a y
F a u l t N a m e
cpf го
or
<
1
>
CPF20 or CPF21
Control Circuit Error
C a u s e
P o s s i b l e S o l u t i o n
Hardware is damaged.
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
D i g i t a l O p e r a t o r D i s p l a y
F a u l t N a m e
c p f
?г
CPF22
Hybrid IC Failure
C a u s e
P o s s i b l e S o l u t i o n
Hybrid IC failure on the power board
• Cycle power to the drive. R efer to D ia g n o sin g a n d R esettin g F au lts on p a g e 2 6 6 .
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
D i g i t a l O p e r a t o r D i s p l a y
F a u l t N a m e
CPFE3
CPF23
Control Board Connection Error
Connection error between the control board and the drive
C a u s e
P o s s i b l e S o l u t i o n
Hardware is damaged.
• Turn the power o ff and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
D i g i t a l O p e r a t o r D i s p l a y
F a u l t N a m e
CPFE4
CPF24
Drive U nit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).
C a u s e
P o s s i b l e S o l u t i o n
Hardware is damaged.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
D i g i t a l O p e r a t o r D i s p l a y
F a u l t N a m e
CPF3S
CPF25
Terminal Board not Connected
C a u s e
P o s s i b l e S o l u t i o n
Terminal board is not connected correctly.
Reconnect the terminal board to the connector on the drive, then cycle the power to the drive.
D i g i t a l O p e r a t o r D i s p l a y
F a u l t N a m e
CPF ?Б
to
CPF 34
CPF26 to CPF34
Control Circuit Error
CPU error
C a u s e
P o s s i b l e S o l u t i o n
Hardware is damaged.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa representative for
instructions on replacing the control board.
242