5.9 n: Special Adjustments
■ n8-33: d-Axis Current Control Integral Time during Normal Operation
Sets the d-Axis integral time for the automatic current regulator.
No.
Name
Setting Range
Default
n8-33
d-Axis Current Control Integral Time during Normal Operation
0.0 to 100.0 ms
10.0 ms
■ n8-62: Output Voltage Limit
Sets the output voltage limit to prevent voltage saturation of the motor. Avoid setting this value higher than the input
voltage on the motor nameplate to maintain optimum motor performance.
No.
Name
Setting Range
Default
n8-62 <1>
Output Voltage Limit
0.0 to 230.0 Vac
200 Vac
<1> Values shown here are for 200 V class drives. Double values w hen using a 400 V class drive.
♦ n9: Current Detection Adjustments
■ n9-60: A/D Conversion Start Delay
Sets a delay time used for A/D conversion o f the current. This value rarely needs to be changed. However, it can help to
resolve speed ripple problems at constant speed when using a PM motor. Prior to adjusting this value, make sure all other
parameters (motor data, speed loop settings) are adjusted correctly.
No.
Name
Setting Range
Default
n9-60
A /D Conversion Start D elay
0.0 to 40.0 Ц-s
Determined by o2-04
210
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual