background image

 

                                                                                         

 

 

DASSTECH Photovoltaic Grid-

Connected Inverter

 

  [Grid connected type Photovoltaic

 

Inverter] 

DASS 100i 

 

            [DSP-33100E-OD-HV]

 

 

       

Version 1.0 

 

 

 

 

Operation and Installation Manual

 

 

Summary of Contents for Soleaf DASS 100i

Page 1: ...DASSTECH Photovoltaic Grid Connected Inverter Grid connected type Photovoltaic Inverter DASS 100i DSP 33100E OD HV Version 1 0 Operation and Installation Manual...

Page 2: ...ation of the Product 10 2 5 Dimensions of the Product 12 2 6 Configuration of the Photovoltaic System 13 2 7 Features of the Product 14 3 Installation 15 3 1 Transportation 15 3 2 Installation Place 1...

Page 3: ...s 34 4 4 Winding Technology 37 5 Operation 39 5 1 Checklist prior to Operation 39 5 2 Appearance of the Display Window and Functions 39 5 3 Display Window Screen 40 5 4 How to Operate 42 6 Functions 4...

Page 4: ...erter must only be operated with PV arrays of protection class II in accordance with IEC 61730 application class A DSP series inverter shouldn t be connected to any energy source other than PV module...

Page 5: ...nger indicates a hazardous situation which if not avoided will result in death or serious injury Warning indicates a hazardous situation which if not avoided can result in death or serious injury Caut...

Page 6: ...ar safety gloves and personal protective equipment The product is worked on a high pressure All works related with the inverter must be performed by a professional electric engineer The capacitor of t...

Page 7: ...erter which can cause electric shock Check if the DC voltage of the inverter is discharged by using a measurement tool such as volt ohm milliampere VOM after 10 min or longer from power off when wirin...

Page 8: ...n The front or upper surface of the enclosure can be hot which can cause a burn Do not touch the inverter while power is connected or within 30 min after power is disconnected Since the product is on...

Page 9: ...ent normal operation or reduce a lifespan of the product In the worst case the inverter can be broken or incur fatal damage to human bodies Therefore please read carefully and understand thoroughly th...

Page 10: ...hether there is any damage during transportation Inverter TYPE Accessories tools Please contact the office if there are some missing accessories such as the operation and installation manual fixed bra...

Page 11: ...10 2 4 Configuration of the Product Front view...

Page 12: ...11 Side view Rear view...

Page 13: ...ication IN OUT ANT Wifi cable option AC Output Port Output AC cable gland Protective Vent Pressure balance Vent F G Grounding connection terminal COM3 COM4 Active voltage control communication IN OUT...

Page 14: ...iguration and connection it can cause abnormal operation or reduce a lifespan of the product seriously In the worst case the inverter can be damaged so please use the product well according to the con...

Page 15: ...less type it is suitable for distributed power systems designed for a commercial scale generation Distributed power system and economic feasibility The photovoltaic system can be installed anywhere w...

Page 16: ...portation Please transport the product correctly according to the weight of the product Do not stack the product beyond the restricted limit Move the unit by 4 persons or more or with the lifting devi...

Page 17: ...wall as much as possible A lifespan of the inverter can be affected by an ambient temperature Please make sure the ambient temperature at the installed place does not exceed an allowable storage tempe...

Page 18: ...d dust as well as direct sunlight and the product should not be close to high temperature heat generating part Generated power can be reduced due to overheating The installation work must be done by p...

Page 19: ...nstallation completion the inverter should be ON and then make the inverter operated At least 60cm of space at the upper part as well as left and right side of the inverter should be secured when the...

Page 20: ...nverter is placed on the bracket and fastened by the bolts Caution At least 4 or more persons must install the inverter during lifting or fixing it to the bracket Because the product is heavy pls inst...

Page 21: ...awings provided along with the inverter Please refer to the drawing as below to make holes 3 points on the location for fixing a bracket Fix the bracket by using bolts and nuts After lifting the inver...

Page 22: ...g AC connectors The wiring work or inspection should be done by professional technician Wiring work should be done after installing the main body of the inverter Cables are not provided separately If...

Page 23: ...e the bracket to the body The inverter must be grounded with special 3 type grounding resistance is 10 or less to prevent electric shock Fasten the grounding of the inverter to the internal grounding...

Page 24: ...cient during wiring of the solar cell module If the output voltage of the solar cell array is set without consideration of temperature coefficient input over voltage or low voltage in the inverter can...

Page 25: ...ection AC Connection Cover can be opened by loosening 2 bolts in the bottom part AC circuit breaker can be found by opening the cover as above Please use a wire of 70SQ for AC wiring pls change the wi...

Page 26: ...minal do not have a phase to phase short circuit among R S T and N Wires and terminal lug should be desigend for 95 at least and Tightening torque should be 5 N m Caution In case of negative phase a c...

Page 27: ...Q or thicker Please press a terminal against the grounding wire and connect the wire to grounding bus bar in the bottom part of the inverter A rated dimension of the terminal is 5 The grounding points...

Page 28: ...27 3 9 RS485 Communication Connection In case of parallel connection pls use two cable glands for communication Open the cover in the bottom part of the inverter RS485 Communication terminal...

Page 29: ...ON the switch in the above pic only in the inverter at the far end of RS485 communication when parallel operation of the inverter and monitoring on the inverter are connected System ID Number should b...

Page 30: ...m ID Number assigning the preferred ID Number to be used Connect DER AVM to a PORT for inverter active voltage control In case of using independently Assign communication ID as above Set Active Voltag...

Page 31: ...1 Technical properties The MV transformer that is connected to the photovoltaic inverter without transformer shall comply with the following technical specifications 1 The transformer shall be suitabl...

Page 32: ...t each installation site shall be considered during thermal rating 7 It is recommended to adjust a voltage level in the mid voltage grid using the transformer which has a tap changer at the high volta...

Page 33: ...be determined when the voltage in other low voltage winding increases until the high voltage winding is short circuited and a nominal current flows The equivalent series impedance Z of the two windin...

Page 34: ...rs in the low voltage side this neutral point shall not be connected or grounded A two winding transformer where winding changes in each of the high voltage and low voltage sides can be used For examp...

Page 35: ...er shall comply with the following technical specifications Equivalent series impedance between low voltage and high voltage windings The equivalent series impedance Z of the transformer shall be 6 in...

Page 36: ...gs shall be 10 The allowable error limit of the impedance voltage shall maintain 9 to 11 This value can be determined when the voltage in other low voltage winding increases until one of the low volta...

Page 37: ...winding and ZL refers to the equivalent series impedance of the high voltage winding A neutral point is not needed in the low voltage side Nonetheless if a neutral point appears in the low voltage sid...

Page 38: ...MV transformer that is connected to the photovoltaic inverter without transformer shall be designed as a section winding transformer Single layer winding transformer Case 1 Double stack Case 2 Triple...

Page 39: ...38 LVW Low voltage winding HVW High voltage wingding Multi layer winding transformer Case 1 LLH Case 2 LLLH...

Page 40: ...then Turn the DC switch to the ON direction The factory default setup of the product is OFF Upon the AC turned ON the inverter counts 300 sec for automatic startup The count time can be checked at the...

Page 41: ...ication in the display window is 128x64 GRAPHIC LCD When power is on in the inverter the display window is converted in every 10 sec automatically 5 3 Display Window Screen RUN Current generated power...

Page 42: ...tg Grid R S interline voltage Line ST Vtg Grid S T line to line voltage Line TR Vtg Grid T R line to line voltage Line R Cur Grid R phase current Line S Cur Grid S phase current Line T Cur Grid T phas...

Page 43: ...peration mode If a voltage in the solar cell module is increased to the setup value due to the sunrise the inverter operates automatically A voltage in the solar cell module is decreased at sunset Onc...

Page 44: ...the solar cell module varies depending on ambient temperature humidity and sunlight the MPPT Maximum Power Point Tracking algorithm should be run smoothly The method applied to the product is that the...

Page 45: ...ation There are two initializations parameter and fault initializations Parameter initialization sets all parameters and optional functions to factory default values while fault initialization removes...

Page 46: ...reaker should be installed additionally 6 3 Types of Main Faults Input over voltage protection If a solar cell voltage exceeds the regulated voltage the system is stopped to protect the inverter Input...

Page 47: ...Grid fault protection Upon the fault occurrence in the grid power the system is stopped Grid over voltage protection grid under voltage protection grid over frequency protection and grid under freque...

Page 48: ...PV OV If the solar cell voltage exceeds the set voltage Operate the inverter after inspecting the solar cell module If the system cannot be rerun please contact the service center 4 Input undervoltage...

Page 49: ...rvice center 13 INSULATION FAULT PV Insulation Insufficient insulation resistance Contact the service center 14 HARDWARE OH Over Heat2 Hardware overheat Contact the service center 15 RCMU FAULT Residu...

Page 50: ...current warning LIMIT_O Maximum output current limit notice When grid voltage is decreased and the inverter s current is over Max value there can be limited current 3 Input current warning LIMIT_I Ma...

Page 51: ...nd failure display description when the product is broken The following items are checked and service repair is requested 1 Model name 2 Manufacture No 3 Purchase place 4 Purchase year 5 Warranty Lett...

Page 52: ...st The connector at the lower part of the inverter The cable glad at the lower part of the inverter DC SWITCH at the lower part of the inverter Dust and humidity of the front display of the inverter I...

Page 53: ...mum input current 178A Control Maximum Power Point Tracking MPPT The number of MPP input 1 Model name DSP 33100E OD HV AC Output Rated power 380V 60Hz 100 000W Rated voltage 400Va c Rated frequency 50...

Page 54: ...nitoring Inverter overheat protection Relay fault detection Grid Anti islanding Short circuit current control Grid overvoltage undervoltage protection Grid overfrequency underfrequency protection Reac...

Page 55: ...A S If failure occurred under normal using condition within the warranty period your product can be tested and repaired for free Charged A S For following cases A S could be provided at a cost The pro...

Page 56: ...Customer service 82 1588 7468 Tel 82 43 218 5670 Fax 82 43 218 5671 Headquarters DASS Tech Co Ltd 81 Yangcheongsongdae gil Ochang eup Cheongwon gu Cheongju si Chungbuk Korea http www dasstech com Ver...