B.3 Parameter Table
♦ F: Option Settings
F parameters are used to program the drive for Encoder and PG feedback from the motor and to function with option
cards.
■ F1: PG Speed Control Card
Setting
Page
Default: <5>
Min: 1 ppr
164
Max: 60000 ppr <34>
Default: 1
Min: 0
164
Max: 3
Default: 1
Min: 0
164
Max: 3
Default: 3
Min: 0
165
Max: 3
Default: 0
Min: 0
165
Max: 1
Default: 1
Min: 1
165
Max: 132
Default: 115%
Min: 0%
164
Max: 120%
Default: 0.0 s
Min: 0.0 s
164
Max: 2.0 s
Default: 10%
Min: 0%
165
Max: 50%
Default: 0.5 s
Min: 0.0 s
165
Max: 10.0 s
Default: 2.0 s
Min: 0.0 s
164
Max: 10.0 s
Default: 10
Min: 0
165
Max: 10
Default: 128
Min: 0
165
Max: 5000
Default: 1
Min: 0
166
Max: 1
Default: 2
Min: 0
166
Max: 2
Default: 0
Min: 0
166
Max: 2
Default: 80%
Min: 1%
166
Max: 100%
No.(Addr.)
F1-01
(380H)
Name
Encoder 1 Resolution
Description
CLV
■
CLV/PM
Sets the encoder resolution (number o f pulses per revolution)
F1-02
(381H)
Operation Selection at PG Open
Circuit (PGo)
CLV
■
CLV/PM
Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
Coast to stop.
Emergency Stop. Decelerate to stop using the deceleration ramp in C1-09.
Alarm only.
F1-03
(382H)
Operation Selection at Overspeed
(oS)
CLV
■
CLV/PM
Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
Coast to stop.
Emergency Stop. Decelerate to stop using the deceleration ramp in C1-09.
Alarm only.
F1-04
(383H)
Operation Selection at Deviation
CLV
В
CLV/PM
Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
Coast to stop.
Emergency Stop. Decelerate to stop using the deceleration ramp in C1-09.
Alarm only.
F1-05
(384H)
Encoder 1 Rotation Direction
Selection
0: A phase leads B in up direction
1: B phase leads A in up direction
F1-06
(385H)
PG 1 Pulse Monitor Output
D ivision Ratio
Sets the division ratio for the pulse monitor used o f the PG option card installed to connector
CN5-C. B y setting “x y z”, the division ratio becom es = [(1 + x) / yz]. If only using the A pulse
for one track input, then the input ratio w ill be 1:1, regardless o f what F1-06 is set to.
F1-08
(387H)
Overspeed Detection Level
Sets the overspeed detection level as a percentage o f the maximum output frequency.
F1-09
(388H)
Overspeed Detection D elay Time
Sets the tim e in seconds for an overspeed situation to trigger a fault (oS).
F1-10
(389H)
E xcessive Speed Deviation
Detection Level
Sets the speed deviation detection level as a percentage o f the maximum output frequency.
F1-11
(38AH)
E xcessive Speed Deviation
Detection Delay Time
Sets the tim e in seconds for a speed deviation situation to trigger a fault (dEv).
F1-14
(38DH)
PG Open-Circuit Detection Time
Sets the tim e required to trigger a PG Open fault (PGo).
F1-18
(3A DH )
dv3 Detection Selection
0: Disabled
n: Sets the number o f dv3 situations that may be detected before triggering an actual dv3 fault.
F1-19
(3AEH)
dv4 Detection Selection
0: Disabled
n: Number o f pulses that the A and B pulse are reversed that triggers dv4 detection.
F1-20
(3B4H)
PG Option Card Disconnect
Detection 1
0: Disabled
1: Enabled
F1-29
(3BFH)
dEv Detection Condition Selection
Selects when DE V is active.
After speed reference, soft starter output and motor speed have matched once.
After speed reference and soft starter output have matched once.
A lw ays during Run
F1-50
(3D2H)
<39>
CLV
■
CLV/PM
Encoder Selection
Selects the encoder connected the PG-F3 option.
0: EnDat 2.1/01, 2.2/01 Serial Communi Sin/Cos
1: EnDat 2.2/22 Serial Communication
2: Hiperface
F1-51
(3D3H)
PGoH Detection Level
CLV
■
CLV/PM
Sets the level for detecting PG Hardware Fault (PGoH). Available when F1-20 = 1
V/f
V/f
V/f
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV/PM
CLV
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
V/f
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
333
P
a
ra
m
e
te
r
L
is
t