5.10 o: Operator Related Settings
■ o2-03: User Parameter Default Value
After completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the
values, parameter A1-03 (Initialize Parameters) will offer the choice o f “ 1110: User Initialize”. Selecting 1110 resets all
parameters to the user-set default values.
Refer to A1-03: Initialize Parameters on page 135
for details on drive
initialization.
No.
Name
Setting Range
Default
o2-03
User Parameter Default Value
0 to 2
0
Setting 0: No change (awaiting command)
Setting 1: Set User Initialize values
The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing
the ENTER key saves the values and returns the display to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for “User Initialize” are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values
and returns the display to 0 .
■ o2-04: Drive Model Selection
This parameter must be set when replacing the control board or the terminal board for any reason. For information on the
drive model selection, refer to
Defaults by Drive Model Selection (o2-04) on page 363.
N OTICE:
D riv e p e rfo rm a n c e w ill s u ffe r a n d p ro te c tiv e fu n c tio n s w ill n o t o p e ra te p ro p e rly i f the c o rre c t drive c a p a c ity is n o t s e t to o2-04.
No.
Name
Setting Range
Default
o2-04
Drive M odel Selection
-
Determined by drive
capacity
■ o2-05: Speed Reference Setting Method Selection
Determines if the ENTER key must be pressed after changing the speed reference using the digital operator while in the
Drive Mode.
No.
Name
Setting Range
Default
o2-05
Speed Reference Setting Method Selection
0 or 1
0
Setting 0: ENTER key required
Every time the speed reference is changed using the digital operator, the ENTER key must be pressed for the drive to
accept the change.
Setting 1: ENTER key not required
The output speed changes immediately when the reference is changed by the up or down arrow keys on the digital
operator. The ENTER key does not need to be pressed. The speed reference is saved for 5 s after it is changed.
■ o2-06: Operation Selection when Digital Operator is Disconnected
Determines whether the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 is set to 0.
When the operator is reconnected, the display will indicate that it was disconnected.
No.
Name
Setting Range
Default
o2-06
D igital Operator Disconnection Operation
0 or 1
0
Setting 0: Continue operation
The operation is continued.
Setting 1: Trigger a fault
The operation is stopped and an “oPr” fault is triggered. The motor coasts to stop.