B.3 Parameter Table
No.(Addr.)
Name
Description
Setting
Page
H 4-04
(420H)
Terminal A M Monitor Selection
S
S
f
elects the data
et the desired m
or U1-03.
ТШШШШШШШШШШШ
I
o be output through m ulti-function analog output terminal AM.
lonitor parameter to the digits available in U D -П П . For example, enter “103”
Default: 103
Min: 000
Max: 999
186
H4-05
(421H)
Terminal A M Gain
S ets the signal level at terminal AM that is equal to 100% o f the selected monitor value.
Default: 50.0%
Min: -999.9%
Max: 999.9%
186
H 4-06
(422H)
Terminal A M Bias
S ets the signal le
Н Н Н В Н Н В Н Н Н В !
v e l at terminal A M that is equal to 0% o f the selected monitor value.
Default: 0.0%
Min: -999.9%
Max: 999.9%
186
H 4-07
(423H )
Terminal FM Signal Level
Selection
0
1
: 0 to 10 V
: - 1 0 to 10 V
Default: 0
Min: 0
Max: 1
188
H4-08
(424H )
Terminal A M Signal Level
Selection
i
0
1
: 0 to 10 V
: - 1 0 to 10 V
Default: 0
Min: 0
Max: 1
188
■ H5: MEMOBUS/Modbus Serial Communication
No.(Addr.)
Name
Description
Setting
Page
H5-01
(425H)
<14>
Drive N ode Address
Selects drive station node number (address) for M EM OBUS/M odbus terminals R+, R-, S+, S-
Cycle power for the setting to take effect.
Default: 1
Min: 0
Max: FF
H 5-02
(426H)
Communication Speed Selection
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
C ycle power for the setting to take effect.
Default: 3
Min: 0
Max: 8
372
H5-03
(427H)
Communication Parity Selection
0: N o parity
1: Even parity
2: Odd parity
C ycle power for the setting to take effect.
Default: 0
Min: 0
Max: 2
H 5-04
(428H )
Stopping Method After
Communication Error (CE)
Ramp to stop
Coast to stop
Emergency Stop
Alarm only
Default: 3
Min: 0
Max: 3
372
H5-05
(429H )
Communication Fault Detection
Selection
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault w ill occur.
Default: 1
Min: 0
Max: 1
H 5-06
(42A H )
Drive Transmit Wait Time
Sets the wait time between receiving and sending data.
Default: 5 ms
Min: 5 ms
Max: 65 ms
H 5-07
(42BH)
RTS Control Selection
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
Default: 1
Min: 0
Max: 1
373
H 5-09
(435H )
Communication Fault Detection
Time
Sets the tim e required to detect a communications error. Adjustment may be needed when
networking several drives.
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
H5-10
(436H)
U nit Selection for M EM O BU S/
Modbus Register 0025H
0: 0.1 V units
1: 1 V units
Default: 0
Min: 0
Max: 1
H5-11
(43CH)
Communications ENTER Function
Selection
0: Drive requires an Enter command before accepting any changes to parameter settings.
1: Parameter changes are activated immediately without the Enter command.
Default: 0
Min: 0
Max: 1
С
<14> I f this param eter is set to 0, the drive will be unable to respond to M EM O BUS/M odbus commands.
372
372
373
373
373
373
374
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
341
P
a
ra
m
e
te
r
L
is