B.5 Defaults by Drive Model Selection (o2-04)
Table B.5 400 V Class Drives Default Settings by Drive Capacity
No.
Name
Unit
Default Settings
-
Model CIMR-LC
-
4A0009
4A0015
4A0018
4A0024
4A0031
4A0039
4A0045
o2-04
Drive Model Selection
Hex.
97
99
9A
9C
9D
9E
9F
E2-11
Motor Rated Output
kW
4.0
5.5
7.5
11
15
18.5
22
C5-17
(C5-37)
Motor Inertia
kgm2
0.0158
0.026
0.037
0.053
0.076
0.138
0.165
C6-03
Carrier Frequency
kHz
8
8
8
8
8
8
8
E2-01
(E4-01)
Motor Rated Current
A
7
9.8
13.3
19.9
26.5
32.9
38.6
E2-02
(E4-02)
Motor Rated Slip
Hz
2.7
1.5
1.3
1.7
1.6
1.67
1.7
E2-03
(E4-03)
Motor No-Load Current
A
2.3
2.6
4
5.6
7.6
7.8
9.2
E2-05
(E4-05)
Motor Line-to-Line Resistance
Q
3.333
1.595
1.152
0.922
0.55
0.403
0.316
E2-06
(E4-06)
Motor Leakage Inductance
%
19.3
18.2
15.5
19.6
17.2
20.1
23.5
E2-10
(E4-10)
Motor Iron Loss for Torque Compensation
W
130
193
263
385
440
508
586
E3-08
Motor 2 M id Output Frequency Voltage
V
37.2
37.2
37.2
37.2
37.2
37.2
37.2
E3-10
Motor 2 M inimum Output Frequency Voltage
V
19.4
19.4
19.4
19.4
19.4
19.4
19.4
E5-02
Motor Rated Power
kW
4.0
5.5
7.5
11
15
18.5
22
E5-03
Motor Rated Current
A
7.3
10
14.6
19
26.6
32.5
38.2
E5-05
Motor Stator Resistance
Q
1.326
1.479
0.892
0.613
0.378
0.276
0.217
E5-06
Motor d-Axis Inductance
mH
19.11
21.58
14.33
13.84
9.85
7.95
6.8
E 5-07
Motor q-Axis Inductance
mH
26.08
29.44
19.56
19.83
14.79
11.94
10.22
E5-09
Motor Induction Voltage Constant 1
mV/(rad/sec)
478.6
508.4
473.9
540
508.4
513.7
522.3
L8-02
Overheat Alarm L evel
°C
110
110
115
120
120
115
120
L8-06
Input Phase Loss Detection Level
%
14.0
26.0
26.0
21.0
22.0
26.0
18.0
n5-02
Motor Acceleration Time
s
0.154
0.168
0.175
0.265
0.244
0.317
0.355
L8-35
Installation Method Selection
-
2
2
2
2
2
2
0
n9-60
A /D Conversion Start Delay
^sec
14.0
14.0
14.0
14.0
14.0
114.0
14.0
No.
Name
Unit
Default Settings
-
Model CIMR-LC
-
4A0060
4A0075
4A0091
4A0112
4A0150
4A0180
4A0216
o2-04
Drive Model Selection
Hex.
A1
A2
A3
A4
A5
A6
A7
E2-11
Motor Rated Output
kW
30
37
45
55
75
90
110
C5-17
(C5-37)
Motor Inertia
kgm2
0.220
0.273
0.333
0.49
0.90
1.10
1.90
C6-03
Carrier Frequency
kHz
8
5
5
5
5
2
2
E2-01
(E4-01)
Motor Rated Current
A
52.3
65.6
79.7
95
130
156
190
E2-02
(E4-02)
Motor Rated Slip
Hz
1.8
1.33
1.6
1.46
1.39
1.4
1.4
E2-03
(E4-03)
Motor No-Load Current
A
10.9
19.1
22
24
36
40
49
E2-05
(E4-05)
Motor Line-to-Line Resistance
Q
0.269
0.155
0.122
0.088
0.092
0.056
0.046
E2-06
(E4-06)
Motor Leakage Inductance
%
20.7
18.8
19.9
20
20
20
20
E2-10
(E4-10)
Motor Iron Loss for Torque Compensation
W
750
925
1125
1260
1600
1760
2150
E3-08
Motor 2 Mid Output Frequency Voltage
V
37.2
37.2
37.2
32.0
32.0
32.0
32.0
E3-10
Motor 2 Minimum Output Frequency Voltage
V
19.4
19.4
19.4
16.6
16.6
16.6
16.6
E5-02
Motor Rated Power
kW
30
37
45
55
75
90
110
E5-03
Motor Rated Current
A
51.8
66.6
74.7
90.8
130.0
130
130
E5-05
Motor Stator Resistance
Q
0.165
0.107
0.087
0.064
0.022
0.022
0.022
E5-06
Motor d-Axis Inductance
mH
5.15
3.62
3.59
2.87
1.80
1.80
1.80
E 5-07
Motor q-Axis Inductance
mH
8
5.63
5.55
4.44
2.80
2.80
2.80
E5-09
Motor Induction Voltage Constant 1
mV/(rad/sec)
520.8
490.2
552
554.4
1280.0
1280.0
1280.0
L8-02
Overheat Alarm Level
°C
120
110
120
130
130
120
120
L8-06
Input Phase Loss Detection Level
%
17.0
18.0
20.0
20.0
29.0
17
25
n5-02
Motor Acceleration Time
s
0.323
0.32
0.387
0.317
0.533
0.592
0.646
L8-35
Installation Method Selection
-
0
0
0
0
0
0
0
n9-60
A /D Conversion Start Delay
^sec
14.0
14.0
14.0
14.0
14.0
14.0
14.0
364
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual