5.4 d: Reference Settings
■ d1-27: Motor 2 Speed Reference
Sets the speed reference for motor 2.
No.
Name
Setting Range
Default
d1-27
Motor 2 Speed Reference
0.00 to 120.00 Hz
0.00 Hz
N ote: 1. The drive will control m otor 1 w hen this param eter is set to 0.00.
2. Set the accel/decel times in parameters C1-12 and C1-13 w hen using m otor 2.
3. W hen m otor 2 is selected, the following monitors will display values in Hz: U1-01, U 1-02, U1-05, U 4-19, U4-20.
■ d1-28: Leveling Speed Detection Level
When the speed priority selection in d1-18 is set to “0” or “3” and the speed reference value falls below the level set in
d1-28, the drive interprets the selected speed as leveling speed. This parameter must be set to use the Speed Control Loop
setting 3 when d1-18 = 0/3. Refer to
C5: Speed Control Loop on page 150
for details.
No.
Name
Setting Range
Default
d1-28
Leveling Speed Detection Level
0.0 to 100.0%
0.0%
■ d1-29: Inspection Speed Detection Level
When the speed priority selection in d1-18 is set to “0” or “3” and the speed reference value is below the level set in d1-
29 but higher than the level set in d1-28, the drive interprets the selected speed as inspection speed. This parameter must
be set to use the Inspection Operation function when d1-18 = 0/3. Refer to
Inspection Operation on page 109
for details.
No.
Name
Setting Range
Default
d1-29
Inspection Speed Detection Level
0.0 to 100.0%
0.0%
♦ d6: Field Forcing
Field Forcing
The Field Forcing function compensates the delaying influence of the motor time constant when changing the excitation
current reference. Field Forcing can improve the motor responsiveness. It is ineffective during DC Injection Braking.
■ d6-03: Field Forcing Selection
Enables or disables the Field Forcing function.
No.
Parameter Name
Setting Range
Default
d6-03
Field Forcing Selection
0 or 1
0
Setting 0: Disabled
Setting 1: Enabled
■ d6-06: Field Forcing Limit
Sets the maximum level at which the Field Forcing function can boost the excitation current reference. The value is set as
a percentage o f the motor no load current. This parameter does not normally need to be changed.
No.
Parameter Name
Setting Range
Default
d6-06
Field Forcing Limit
100 to 400%
400%
156