B.3 Parameter Table
H2 Multi-Function Digital Output Settings
H 2-D D
Setting
Function
1C
Motor 2 Selection
1D
During Regeneration
1E
R eset Enabled
1F
Motor Overload Alarm (oL1)
20
D rive Overheat Pre-alarm (oH)
2F
Maintenance Period
30
During Torque Limit
33
Within Position Lock Bandwidth
37
During Frequency Output
47
Input Phase Loss
4E
Braking Transistor Fault (rr)
50
Brake Control
51
Output Contactor Control
52
Door Zone Reached
53
N ot Zero Speed
54
Light Load Direction
55
Light Load Direction Detection
Status
58
Safe D isable Status
60
Internal Cooling Fan Alarm
61
Motor Pole Search Status
100 to 161
Function 0 to 61 with Inverse Output
Description
CLV
■
CLV/PM
Open: Motor 1 is selected
Closed: Motor 2 is selected
Page
181
CLV
■
CLV/PM
Closed: Motor is operated in regenerative mode.
181
Closed: A n automatic reset is performed
Closed: oL1 is at 90% o f its trip point or greater. A n oH3 situation also triggers this alarm.
181
Closed: Heatsink temperature exceeds the parameter L8-02 value.
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require maintenance.
181
CLV
В
CLV/PM
Closed: W hen the torque limit has been reached.
182
CLV
■
CLV/PM
Closed: Position deviation is within the Position Lock Bandwidth.
Open: Either the drive has stopped or baseblock, D C Injection Braking, or Initial Excitation is being performed.
Closed: D rive is running the motor (not in a baseblock state and DC Injection is not being performed).
Closed: Input phase loss has occurred
Open: Normal operation (no phase loss detected)
Closed: The built-in dynamic braking transistor failed.
N o t e :
This function is not available in m odels C IM R -L D 2A 0145 to 2A0415, 4A 0075 to 4A0216.
Close: R elease brake
Open: Apply brake
Closed: C lose output contactor
Closed: Indicates that the door zone has been reached.
182
Closed: Speed is greater than the zero speed level set to S1-01
Open: Operating at zero speed level
Closed: Light load direction is up
Open: Light load direction is down
Closed: Ready for Light Load Direction Search
Open: Light Load D etection in progress
182
Closed: Safe D isable terminals H1-HC and H2-HC are open, drive is in a baseblock state
Open: Safe D isable terminals H1-HC and H2-HC are closed (normal operation)
183
Closed: Internal cooling fan alarm
183
CLV
В
CLV/PM
Closed: Motor pole search successful
183
Inverts the output switching o f the m ulti-function output functions.
Sets the last two digits o f 1 □ □ to reverse the output signal o f that specific function.
183
С
V/f
V/f
181
181
V/f
V/f
182
182
182
182
182
182
182
182
V/f
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
339