B.3 Parameter Table
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 7).
■ E4: Motor 2 Parameters
No.(Addr.)
Name
E4-01
(321H)
Motor 2 Rated Current
E4-02
(322H)
Motor 2 Rated Slip
E4-03
(323H)
Motor 2 Rated N o-Load Current
E 4-04
(324H)
Motor 2 Motor Poles
E4-05
(325H)
Motor 2 Line-to-Line Resistance
E 4-06
(326H)
Motor 2 Leakage Inductance
Setting
Page
Default: <4>Min: 10%
o f drive rated current
Max:
200% o f drive rated
current <10>
161
Default: <4>
Min: 0.00 Hz
Min: 20.00 Hz
162
Default: <4>
Min: 0 A
Min: [E4-01] <10>
162
Default: 4
Min: 2
Max: 48
162
Default: <4>
Min: 0.000 Q
Max: 65.000 Q
162
Default: <4>
Min: 0.0%
Max: 40.0%
162
Description
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
Sets the no-load current for motor 2. Automatically set during Auto-Tuning.
Sets the number o f poles o f motor 2. Automatically set during Auto-Tuning.
Sets the phase-to-phase resistance for motor 2. Automatically set during Auto-Tuning.
Sets the voltage drop for motor 2 due to motor leakage inductance as a percentage o f rated
voltage. Automatically set during Auto-Tuning.
<4> D efault setting value is dependent on the drive model (o2-04).
<10> The display resolution depends on the rated output power o f the drive. M odels CIM R -LD 2A 0018 to 0033 and CIMR-LIH4A0009 to 0018
display values in 0.01 A units, while models CIM R -LD 2A 0047 to 0415 and C IM R -LD 4A 0024 to 0216 display values in 0.1 A units.
■ E5: PM Motor Settings
Setting
Page
Default: <4>
Min: 0.10 kW
Max: 650.00 kW
162
Default: <4>
Min: 10% o f drive rated
current
Max: 200% o f drive
rated current <10>
163
Default: 12
Min: 2
Max: 48
163
Default: <4>
Min: 0.000 Q
Max: 65.000 Q
163
Default: <4>
Min: 0.00 mH
Max: 600.00 mH
163
Default: <4>
Min: 0.00 mH
Max: 600.00 mH
163
Default: <4>
Min: 0.0 mV/(rad/s)
Max:
6500.0 mV/(rad/s)
163
Default: 0.0 deg
Min: -180 deg
Max: 180 deg
163
Default:
0.0 m V/(r/min)
Min:
0.0 m V/(r/min)
Max:
6500.0 m V/(r/min)
163
No.(Addr.)
E5-02
(32A H )
<1>
Name
Motor Rated Power
[
V/f
OLV
Ж
CLV
■
CLV/PM
]
Sets the rated capacity o f the motor.
[
V/f
1 1
OLV
■
CLV
■
CLV/PM
]
E5-03
(32BH)
<1>
Motor Rated Current
Sets the motor rated current.
E 5-04
(32CH)
<1>
Number o f Motor Poles
CLV
■
CLV/PM
Sets the number o f motor poles.
E5-05
(32D H )
<1>
Motor Stator Resistance
(Single Phase)
V/f
■
OLV
■
CLV
■
CLV/PM
Sets the stator resistance (1 phase value).
E 5-06
(32EH)
<1>
Motor d-Axis Inductance
CLV
■
CLV/PM
Sets the d-axis inductance.
E 5-07
(32FH)
<1>
Motor q-Axis Inductance
V/f
■
OLV
■
CLV
■
CLV/PM
Sets the q-axis inductance.
E 5-09
(331H)
<1>
Motor Induction Voltage Constant 1
V/f
■
OLV
■
CLV
■
CLV/PM
Sets the induced phase peak voltage in units o f 0.1 m V (rad/s) [electrical angle].
W hen setting this parameter, E 5-24 should be set to 0.0.
E5-11
(333H)
Encoder Offset
CLV
■
CLV/PM
Sets the offset between the rotor magnetic axis and the encoder zero position. Set during
Encoder Offset Tuning.
E5-24
(353H)
Motor Induction Voltage Constant 2
V/f
■
OLV
■
CLV
■
CLV/PM
Sets the induced phase-to-phase rms voltage in units o f 0.1 mV/(r/min) [mechanical angle].
W hen setting this parameter, E 5-09 should be set to 0.0.
<1> Param eter setting value is not reset to the default value when the drive is initialized.
<4> D efault setting value is determined by the drive model (o2-04).
<10> The display resolution depends on the rated output power o f the drive. M odels CIM R-LC2A0018 to 2A0033 and CIM R-LC4A0009 to
4A 0018 display values in 0.01 A units, while models CIM R-LC2A0047 to 2A0415 and CIM R-LC4A0024 to 4A 0216 display values in 0.1 A
units.
V/f
CLV/PM
CLV
V/f
CLV/PM
CLV
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
CLV
CLV/PM
V/f
V/f
V/f
332