D.2 European Standards
■ EMC Filters
Install the drive with the EMC filters to comply with the EN61800-3/EN12015 requirements.
Note: I f the Safe D isable function o f the drive is part o f the safety concept o f a machine or installation and used for a safe stop
according to EN60204-1, stop category 0, use these filters recom mended by Yaskawa. For all other EM C filters, additional
m easurem ents must be performed to prove EM C compatibility. This also applies when using the safe disable function in one
m otor contactor installations as described in
Safe D isable In p u t F u n c tio n on page 410.
Table D.1 EN61800-3 Filters
Model
CIMR-LD
Filter Data (Manufacturer: Schaffner)
Type
Rated Current (A)
Weight
(kg)
Dimensions
[W x D x H]
(mm)
Y x X
Figure
T h r e e - P h a s e 2 0 0 V C la s s
2 A 0 0 1 8
F S5972-35-07
35
2.1
206 x 50 x 355
1 7 5 x 336
1
2 A 0 0 2 5
2 A 0 0 3 3
F S5972-60-07
60
4.0
236 x 65 x 408
205 x 390
2 A 0 0 4 7
2 A 0 0 6 0
FS5972-100-35
100
3.4
90 x 150 x 330
65 x 255
2
2 A 0 0 7 5
2 A 0 1 8 5
FS5972-170-40
170
6.0
120 x 170 x 451
1 0 2 x 365
2 A 0 1 1 5
2 A 0 1 4 5
FS5972-250-37
250
11.7
130 x 240 x 610
90 x 498
2 A 0 1 8 0
2 A 0 2 1 5
FS5972-410-99
410
10.5
260 x 115 x 386
2 3 5 x 120
3
2 A 0 2 8 3
2 A 0 3 4 6
FS5972-600-99
600
11
260 x 135 x 386
2 3 5 x 120
2 A 0 4 1 5
T h r e e - P h a s e 4 0 0 V C la s s
4 A 0 0 0 9
FS5972-18-07
18
1.3
141 x 46 x 330
115 x 313
1
4 A 0 0 1 5
FS5972-35-07
35
2.1
206 x 50 x 355
1 7 5 x 336
4 A 0 0 1 8
4 A 0 0 2 4
4 A 0 0 3 1
FS5972-60-07
60
4
236 x 65 x 408
202 x 390
4 A 0 0 3 9
4 A 0 0 4 5
4 A 0 0 6 0
FS5972-100-35
100
3.4
90 x 150 x 330
65 x 255
2
4 A 0 0 7 5
4 A 0 0 9 1
FS5972-170-35
170
6.0
120 x 170 x 451
1 0 2 x 365
4 A 0 1 1 2
4 A 0 1 5 0
4 A 0 1 8 0
FS5972-250-37
250
11.7
130 x 240 x 610
90 x 498
4 A 0 2 1 6
FS5972-410-99
410
10.5
260 x 115 x 386
2 3 5 x 120
3
i d
:
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual