B.3 Parameter Table
No.(Addr.)
F1-52
(3D 4H )
<39>
Name
Description
Communication Speed o f Serial
Encoder Selection
Selects the communication speed between the PG-F3 option and serial encoder.
1M bps/9600 bps
500k bps/19200 bps
1M bps/38400 bps
1M bps/38400 bps
Setting
Page
Default: 0
Min: 0
1 67
Max: 3
Default: 0
Min: 0
1 67
Max: 1
F1-63
(2DFH)
PG-E3 R Track Selection
0: Disabled
1: Enabled
V/f
CLV
CLV/PM
<5> D efault setting is determined by the control mode (A1-02).
<34> Setting range is 1 to 15000 ppr when the drive is set for CLV/PM.
<39> Available in drive software versions PRG : 7016 and later.
■ F3: Digital Input Card (DI-A3)
No.(Addr.)
Name
Description
Setting
Page
F3-01
(390H)
DI-A3 Option Card Input Selection
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 H z units
4: BCD, 0.1 H z units
5: BCD, 0.01 H z units
6: BCD customized setting (5 digit), 0.02 H z units
7: Binary input
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 40961/100% (-4095 to + 4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
W hen the digital operator units are set to be displayed in Hertz or user-set units (o1-03 = 2
the units for F3-01 are determined by parameter o1-03.
Default: 0
Min: 0
Max: 7
1 67
or 3),
F3-03
(3B 9H )
DI-A3 Option Card Data Length
Selection
8 bit
12 bit
16 bit
Default: 2
Min: 0
Max: 2
168
■ F4: Analog Monitor Card (AO-A3)
No.(Addr.)
Name
|
Description
Setting
Page
F4-01
(391H)
Terminal V1 Function Selection
г
Default: 102
Min: 000
Max: 999
168
i All Modes
Sets the monitor signal for output from terminal V1. Set this parameter to the last three digits o f
the desired U D - П П monitor. Some U parameters are available only in certain control modes.
F4-02
(392H)
Terminal V1 Gain
Default: 100.0%
Min: -999.9%
Max: 999.9%
168
1 All Modes
| Sets the gain for voltage output via terminal V1.
F4-03
(393H)
Terminal V2 Function Selection
г
Default: 103
Min: 000
Max: 999
168
1 All Modes
Sets the monitor signal for output from terminal V2. Set this parameter to the last three digits o f
the desired U D - П П monitor. Some U parameters are available only in certain control modes.
F4-04
(394H)
Terminal V2 Gain
Default: 50.0%
Min: -999.9%
Max: 999.9%
168
1 All Modes
| Sets the gain for voltage output via terminal V2.
F4-05
(395H)
Terminal V1 Bias
Default: 0.0%
Min: -999.9%
Max: 999.9%
168
1 All Modes
| Sets the amount o f bias added to the voltage output via terminal V1.
F4-06
(396H)
Terminal V2 Bias
Default: 0.0%
Min: -999.9%
Max: 999.9%
168
1 All Modes
Sets the amount o f bias added to the voltage output via terminal V2.
F4-07
Terminal V1 Signal L evel
Default: 1
Min: 0
169
(397H)
Selection
1 All Modes
Max: 1
0 : 0 to 10 V
Default: 1
F4-08
Terminal V2 Signal L evel
1: -10 to 10 V
Min: 0
169
(398H)
Selection
Max: 1
334
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual