B.3 Parameter Table
No. (Addr.)
Name
Description
Setting
Page
o4-12
(512H)
kWh Monitor Initialization
Default: 0
Min: 0
Max: 1
2 1 7
i
All Modes
0: U 4-10 and U 4 -1 1 monitor data is not reset when the drive is initialized (A1-03).
1: R esets the kWh counter. The monitors U 4-10 and U4-11 w ill display "0" after they are
initialized. Once o4-12 is set to 1 and the ENTER key is pressed, kWh data is erased and the
display returns to 0.
o4-13
(528H)
Number o f Travels Counter Reset
Default: 0
Min: 0
Max: 1
2 1 7
I
All Modes
0: Keep the number o f travels counter value. The counter is not reset when the drive is
initialized (A1-03).
1: Resets the number 0 travels counter. The monitor U 4-24/25 w ill show 0. Once o4-13 is set to
1 and the ENTER key is pressed, the counter value is erased and the display returns to 0.
o4-15
(537H)
<1>
Maintenance Alarm Snooze Period
Default: 2%
Min: 0%
Max: 20%
2 1 7
I
All Modes
After a maintenance alarm output has been triggered, o4-15 determines the level that w ill
trigger the next alarm for the same component. The same alarm w ill be triggered by the
detection level that triggered the original alarm plus the level set in o4-15.
o4-16
(176H)
<1>
Maintenance Monitoring Selection
Default: 1000
Min: 0000
Max: 1111
2 1 7
I
All Modes
S
0
1
2
3
elects the Maintenance Monitor using bits 0 to 3.
: LT1 (cooling fan)
: LT2 (DC bus capacitors)
: LT3 (soft-charge bypass relay)
: LT4 (IGBTs have passed 90% o f the their life expectancy)
<1> Param eter setting value is not reset to the default value during drive initialization (A1-03).