B.3 Parameter Table
No. (Addr.)
Name
Description
Analog Output
Level
Unit
Page
U1-19
(66H)
D isplays the contents o f a M EM OBUS/M odbus error.
U1 - 1 9 = 0 0 0 0 0 0 0 0
M EM OBUS/M odbus Error
Code
-
1
CRC Error
-
1
Data Length Error
0
Not Used
1
Parity Error
1
Overrun Error
1
Framing Error
-
1
Timed Out
0
Not Used
N o signal output
available
U1-25
(4DH)
Software Number (Flash)
N o signal output
available
U1-26
(5BH)
Software No. (ROM)
N o signal output
available
FLASH ID
ROM ID
<9> Values shown here are for 200 V class drives. Double the value w hen using a 400 V class drive.
<10> The display resolution depends on the rated output power o f the drive. M odels CIM R-LC2A0018 to 2A0033 and CIM R-LC4A0009 to
4A 0018 display values in 0.01 A units, w hile models CIM R-LC2A0047 to 2A0415 and CIM R-LC4A0024 to 4A 0216 display values in 0.1 A
units.
<12> The display resolution depends on the rated output power o f the drive. M odels CIM R-LC2A0018 to 2A0033 and CIM R-LC4A0009 to
4A 0018 display values in 0.01 kW units, while models CIM R-LC2A0047 to 2A0415 and CIM R-LC4A0024 to 4A 0216 display values in 0.1
kW units.
<31> Setting units are determined by the digital operator display unit selection (o1-03). W hen o1-03 = 0, the value is set in Hertz. W hen o1-03 = 4
or 5, the value is displayed in m/s. W hen o1-03 = 6, the value is displayed in ft/min.
■ U2: Fault Trace
No. (Addr.)
Name
Description
Analog Output
Level
Unit
Page
U2-01
(80H)
Current Fault
D isplays the current fault.
N o signal output
available
U 2-02
(81H)
Previous Fault
D isplays the previous fault.
N o signal output
available
U2-03
(82H)
Speed Reference at Previous
Fault
D isplays the speed reference at the previous fault.
N o signal output
available
0.01%
<31>
U 2-04
(83H)
Output Speed at Previous Fault
D isplays the output speed at the previous fault.
N o signal output
available
0.01%
<31>
U2-05
(84H)
Output Current at Previous
Fault
D isplays the output current at the previous fault.
N o signal output
available
U 2-06
(85H)
Motor Speed at Previous Fault
CLV
■
CLV/PM
D isplays the motor speed at the previous fault.
N o signal output
available
0.01%
<31>
U 2-07
(86H)
Output Voltage at Previous
Fault
D isplays the output voltage at the previous fault.
N o signal output
available
U 2-08
(87H)
DC Bus Voltage at Previous
Fault
D isplays the DC bus voltage at the previous fault.
N o signal output
available
1 Vdc
U 2-09
(88H)
Output Power at Previous
Fault
D isplays the output power at the previous fault.
N o signal output
available
0.1 kW
U 2-10
(89H)
Torque Reference at Previous
Fault
CLV
В
CLV/PM
D isplays the torque reference at the previous fault.
N o signal output
available
0.1%
U2-11
(8AH)
Input Terminal Status at
Previous Fault
D isplays the input terminal status at the previous fault. Displayed as in U1-10.
N o signal output
available
U 2-12
(8BH)
Output Terminal Status at
Previous Fault
D isplays the output status at the previous fault. Displays the same status displayed in U1-11.
N o signal output
available
U2-13
(8CH)
Drive Operation Status at
Previous Fault
D isplays the operation status o f the drive at the previous fault. D isplays the same status
displayed in U1-12.
N o signal output
available
U 2-14
(8D H )
Cumulative Operation Time at
Previous Fault
D isplays the cumulative operation tim e at the previous fault.
N o signal output
available
1 h
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
357
<10>
V/f
V/f
P
a
ra
m
e
te
r
L
is
t