5.2 b: Application
5.2
b: Application
♦ b1: Operation Mode Selection
■ b1-01: Speed Reference Selection
Selects the frequency reference source for the REMOTE mode.
N O TIC E:
A lw a y s turn o ff the R U N c o m m a n d b e fo re c h a n g in g the s e ttin g o f p a ra m e te rs d 1 -1 8 (S p e e d R e fe re n c e S ele ctio n M ode), b1-
01 (S p e e d R e fe re n ce S election), o r
Н 1 - П П
(M u lti-F u n c tio n D ig ita l Inputs). I f the R U N c o m m a n d is on w h en c h a n g in g a n y o f these
settings, the m o to r m a y u n e x p e c te d ly start running, a n d c o u ld re s u lt in injury.
Note: 1. I f an U p/D own comm and is input to the drive but the speed reference entered is 0 or below the minim um frequency, the RUN
indicator LED on the digital operator will light.
2. Press the LO /RE key to set the drive to LOCAL and use the digital operator keypad to enter the speed reference.
No.
Parameter Name
Setting Range
Default
b1-01
Speed Reference Selection
0 to 3
0
Setting 0: Operator keypad
When b1-01 = 0, the user can enter the speed reference in the following ways:
• Switch between the speed references set to the d1-D D parameters according to the speed reference priority (d1-18)
and multi-function digital input terminal settings. For more detailed instructions, refer to
d1: Speed Reference on
page 154.
• Enter the speed reference directly using the digital operator keypad.
Instructions on changing speed reference settings can be found in
The Drive and Programming Modes on page 82.
Setting 1: Terminals (analog input terminals)
If source of the speed reference is assigned to the control terminals (b1-01 = 1), then d1-18 will automatically be set to 0
so the drive uses multi-speed references d1-01 to d1-08. With this setting, the analog input terminal can be used to set the
speed reference. The drive will look to analog input terminals A1 or A2 for the speed reference (provided parameter H3-
02 or H3-10 must be set to “0”, assigning terminal A1 or A2 respectively to the speed reference). Parameter d1-18 is to
be set to 0. Refer to
d1: Speed Reference on page 154
for more detailed.
Terminals A1 and A2 can accept a voltage signal to supply the speed reference to the drive.
Table 5.5
shows the
parameter settings and voltage levels required for each terminal.
Table 5.5 Analog Input Settings for Speed Reference Using Voltage Signals
Terminal
Signal Level
Parameter Settings
Notes
Signal Level Selection
Function Selection
Gain
Bias
A1
0 to 10 Vdc
H3-01 = 0
H 3-02 = 0
(speed reference bias)
H3-03
H 3-04
-
-10 to +10 Vdc
H3-01 = 1
A2
0 to 10 Vdc
H3-09 = 0
H 3-10 = 0
(speed reference bias)
H3-11
H3-12
-
-10 to +10 Vdc
H3-09 = 1
Setting 2: MEMOBUS/Modbus Communications
When b1-01 = 2, the speed reference is given to the drive using MEMOBUS/Modbus register 0002H. Setting the speed
Щ
5
reference from MEMOBUS/Modbus requires setting parameter d1-18 to 0.
Note: Be sure to program the digital inputs for speed selection and set param eter b1-02 to 0 w hen switching the preset speeds set in the
d 1 -D D param eters via M EM OBUS/M odbus. Select the desired speed by switching these digital inputs using the M EM OBUS/
M odbus operation comm and (0001H).
Setting 3: Option card
When b1-01 = 3, the drive looks to a serial network option card for the speed reference. Setting the speed reference from
a communication option card requires parameter d1-18 to be set to 0 .
Note: 1. Be sure to program the digital inputs for speed selection and set param eter b1-01 to 0 when switching the preset speeds set in the d1-
□ □ parameters via a com m unication option card. Select the desired speed by switching these digital inputs using the drive operation
comm and (refer to the option card manual for details).
2. I f the speed reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 Operator Programming
Error will be displayed on the digital operator and the drive will not run.
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
139