6 DeviceNet Communications
6.8.3 Sending Explicit Messages Using the CMND Instruction
6-70
6
Message Response Read Timing
Execute response reading by the rising edge of the Network Communications Enabled Flag
for each communications port.
Communication-related Flags
The following table shows the communications-related flags
.
Response read
processing
Network Communications
Enabled Flag
Type
Name
Address
Contents
Word
Bits
SYSMAC flags
Network Com-
munications
Enabled Flag
A202
0: Execution disabled
(Executing.)
1: Execution enabled
(Not executing.)
Network Com-
munications
Execution
Error Flag
A219
0: Normal completion
1: Error
Master Unit status
flags
Message Com-
munications
Enabled Flag
25
×
unit
1524
12
0: Error is read and Master Unit
message communications
are disabled.
1: Master Unit message com-
munications are enabled.
↑
↑ ↑ ↑ ↑ ↑ ↑ ↑
7 6 5 4 3 2 1 0
Port 0
Port 1
Port 6
Port 5
Port 4
Port 3
Port 2
Port 7
↑
↑ ↑ ↑ ↑ ↑ ↑ ↑
7 6 5 4 3 2 1 0
Port 0
Port 1
Port 6
Port 5
Port 4
Port 3
Port 2
Port 7