6.3 Precautions for Communications Line Design
6-19
6
Noise Precautions for Peripheral Devices
Implement the following noise precautions for peripheral devices.
• Install surge suppressors on devices that generate noise, particularly devices that have an
inductive component such as motors, transformers, solenoids, and magnetic coils.
• If a surge suppressor does not fit on the device, such as a contactor, installing a ferrite
core directly next to the device’s contactors may be effective.
• Insert a line filter on the primary side of the communications power supply.
• When there are two or more communications power supplies, the DeviceNet special
cables can be grounded by simply connecting a single Power Supply Tap near the center
of the DeviceNet special cable. Do not ground shield wire at more than one place.
Device (such as a motor)
Surge suppressor
(Installed next to device.)
Surge suppressor
(Installed next to device.)
DC input type
AC input type
Device (such as a motor)
Ferrite Core 0443-164151
(made by Nisshin Electric Co, Ltd.), etc.
PS
Master
Slave
xxxxxx
[When There Is One Power Supply]
PS
Master
Slave
xxx
xxx
Power Supply Tap
PS
PS
[When There Are Two or More Power Supplies]
T-branch Tap or Power Supply Tap
Power Supply Tap
Power Supply Tap
Slave
Ground at only one point.
Summary of Contents for OMNUC W R88A-NCW152-DRT
Page 1: ...Cat No I538 E3 1 DeviceNet Option Unit OMNUC W Series Model R88A NCW152 DRT...
Page 53: ...4 Connectors 4 5 3 DeviceNet Network Configuration Restrictions 4 22 4...
Page 97: ...5 Parameter Settings 5 3 8 Notch Signal Output Positioning 5 44 5...
Page 211: ...8 Servo Driver Settings 8 5 3 Absolute Encoder Multi turn Limit Setting 8 24 8...
Page 257: ...9 Troubleshooting 9 46 9...