9.3 Troubleshooting with Alarm Displays
9-9
9
A.10
A.10: Overcurrent
Display and Outputs
Note
OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
Note
E to H can occur with 200-V Servo Driver models for 1.5 to 5 kW.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
ON
OFF
OFF
OFF
Cause
Remedy
A
Wiring shorted between Servo Driver and
Servomotor.
Check and correct wiring.
B
Servomotor phase U, V, or W shorted.
Replace the Servomotor.
C
• Circuit board (1PWB) is defective.
• Power transistor is defective.
Replace the Servo Driver.
D
Current feedback circuit, power transistor,
DB relay, or circuit board is defective.
Replace the Servo Driver.
E
The ambient temperature of the Servo
Driver exceeded 55
°
C.
Alter conditions so that the ambient tem-
perature goes below 55
°
C.
F
The air flow around the heat sink is bad.
Follow the installation method and provide
sufficient space as specified.
G
Fan stopped.
Replace the Servo Driver.
H
The Servo Driver is operating under an
overload.
Reduce load.
At power ON
C
A, B, D, E,
F, G, H
C, D
During Servomotor
operation
When SERVO ON
(RUN) signal turned ON
Summary of Contents for OMNUC W R88A-NCW152-DRT
Page 1: ...Cat No I538 E3 1 DeviceNet Option Unit OMNUC W Series Model R88A NCW152 DRT...
Page 53: ...4 Connectors 4 5 3 DeviceNet Network Configuration Restrictions 4 22 4...
Page 97: ...5 Parameter Settings 5 3 8 Notch Signal Output Positioning 5 44 5...
Page 211: ...8 Servo Driver Settings 8 5 3 Absolute Encoder Multi turn Limit Setting 8 24 8...
Page 257: ...9 Troubleshooting 9 46 9...