9.3 Troubleshooting with Alarm Displays
9-43
9
CPF01
CPF01: Parameter Unit Transmission Error 2
This alarm is not stored in the alarm record function memory.
Display and Outputs
Status and Remedy for Alarm
A.- -
A.- -: Normal Operation
This is not an alarm display.
Display and Outputs
Note
OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
Not specified
Cause
Remedy
A
Cable defective or poor contact between
Parameter Unit and Servo Driver
• Check connector connections.
• Replace cable.
B
Malfunction due to external noise
Separate Parameter Unit and cable from
noise source.
C
Parameter Unit is defective.
Replace Parameter Unit.
D
The Servo Driver is defective.
Replace the Servo Driver.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
OFF
ON
A, B, C, D
During operation