9.3 Troubleshooting with Alarm Displays
9-37
9
A.E7
A.E7: DeviceNet Unit Detection Error when the W-series Servo Driver power is ON
A.E7 occurs when the W-series Servo Driver is used without the DeviceNet Unit after it has
been used with the DeviceNet Unit.
Display and Outputs
Note
OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
A.E8
A.E8: Rotary Switch Setting Error on DeviceNet Unit Front Panel
Display and Outputs
Note
OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
ON
ON
OFF
Cause
Remedy
A
The DeviceNet Unit is not mounted
properly.
Check that DeviceNet Unit mounted cor-
rectly.
B
The DeviceNet Unit is not mounted.
Execute Fn014 from Parameter Unit.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
ON
ON
OFF
Cause
Remedy
A
Baud rate setting is incorrect.
Be sure the setting is between 0 and 2.
B
Node address setting is incorrect.
Be sure the setting is between 0 and 63.
A, B
DeviceNet Unit detection
error
A, B
Rotary switch setting error
when power is turned ON
Summary of Contents for OMNUC W R88A-NCW152-DRT
Page 1: ...Cat No I538 E3 1 DeviceNet Option Unit OMNUC W Series Model R88A NCW152 DRT...
Page 53: ...4 Connectors 4 5 3 DeviceNet Network Configuration Restrictions 4 22 4...
Page 97: ...5 Parameter Settings 5 3 8 Notch Signal Output Positioning 5 44 5...
Page 211: ...8 Servo Driver Settings 8 5 3 Absolute Encoder Multi turn Limit Setting 8 24 8...
Page 257: ...9 Troubleshooting 9 46 9...