9 Troubleshooting
9-12
9
A.40
A.40: Main Circuit DC Voltage Error Detected: Overvoltage
Display and Outputs
Note
OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
ON
OFF
Cause
Remedy
A
The power supply voltage is not within the
range of specifications.
Check power supply.
B
Load exceeds capacity of the Regenerative
Unit.
Check specifications of load inertia and
overhanging load.
C
Regenerative transistor is abnormal.
Replace the Servo Driver.
D
Rectifying diode is defective.
E
The Servo Driver is defective.
E
A, B, C, D
A, D
During Servomotor
operation
Occurred when main
circuit power turned ON
Occurred when the control
circuit power turned ON