234
High-speed Counters
Section 7-1
Set the target values so that they do not occur at the peak or trough of count
value changes.
Range Comparison
The specified interrupt task is executed when the high-speed counter PV is
within the range defined by the upper and lower limit values.
• The comparison conditions (upper and lower limits of the range) are regis-
tered in the comparison table along with the corresponding interrupt task
number. The specified interrupt task will be executed once when the high-
speed counter PV is in the range (Lower limit
≤
PV
≤
Upper limit).
• A total of 8 ranges (upper and lower limits) are registered in the compari-
son table.
• The ranges can overlap.
• A different interrupt task can be registered for each range.
• The counter PV is compared with the 8 ranges once each cycle.
• The interrupt task is executed just once when the comparison condition
goes from unmet to met.
Restrictions
When more than one comparison condition is met in a cycle, the first interrupt
task in the table will be executed in that cycle. The next interrupt task in the
table will be executed in the next cycle.
Note
The range comparison table can be used without starting an interrupt task
when the comparison condition is met. The range comparison function can be
useful when you just want to know whether or not the high-speed counter PV
is within a particular range.
Use the Range Comparison Condition Met Flags to determine whether the
high-speed counter PV is within a registered range.
Pausing Input Signal Counting (Gate Function)
If the High-speed Counter Gate Bit is turned ON, the corresponding high-
speed counter will not count even if pulse inputs are received and the counter
PV will be maintained at its current value. Bits A53108 to A53111 are the
High-speed Counter Gate Bits for high-speed counters 0 to 3.
Target value 1
Target value 2
Target value 1
Target value 2
Match not recognized.
Match
Match
Match
No. 255
No. 000
No. 000
No. 255
High-speed counter PV
Comparison is executed
without regard to the
order of the ranges in
the table.
Upper limit 1
Lower limit 1
Upper limit 2
Lower limit 2
Interrupt task that is started.
Time
Comparison table
Upper limit 1
Lower limit 1
Interrupt task = 000
Upper limit 2
Lower limit 2
Interrupt task = 255
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......