358
Inverter Positioning
Section 7-3
PLC Setup
■
Serial Port Communications Settings
Note
(1) Set the baud rate and parity check settings to the same value as for the
Inverter communications parameters.
(2) Set the serial port to the serial gateway communications mode.
n153
RS-422A/485 communications
Slave address
Setting range: 0 to 32
00: Communications disabled
01 to 32: Slave address
0
1
n154
RS-422A/485 baud rate selec-
tion
0: 2,400 bps
1: 4,800 bps
2: 9,600 bps
3: 19,200 bps
2
2
n155
RS-422A/485 parity selection
0: Even
1: Odd
2: No parity
0
0
n156
RS-422A/485 send wait time
Set value: 10 to 65 ms
Setting unit: 1 ms
10 ms
10 ms
n157
RS-422A/485 RTS control
selection
0: RTS control enabled
1: RTS control disabled
0
0
Parameter
No.
Name
Description
Default
Setting
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......