257
Pulse Outputs
Section 7-2
2.
Changing the Pulse Output PV
When you want to set the current position as the origin, execute INI(880)
to reset the pulse output PV to 0.
The origin location can be determined after using either method.
The CP1L-EL/EM CPU Units are also equipped with the origin return function,
which can be executed to return the system to the origin after the origin loca-
tion has been determined by one of the methods above.
• Origin Return
If the motor is stopped, ORG(889) can be executed to perform an origin
return operation that moves the motor back to the origin position. The ori-
gin position must be determined in advance by performing an origin
search or changing the pulse output PV.
Note
The motor can be moved even if the origin position has not been determined,
but positioning operations will be limited as follows:
• Origin return: Cannot be used.
• Positioning with absolute pulse specification: Cannot be used.
• Positioning with relative pulse specification: Outputs the specified number
of pulses after setting the current position to 0.
7-2-5-1
Origin Search
When ORG(889) executes an origin search, it outputs pulses to actually move
the motor and determines the origin position using the input signals that indi-
cate the origin proximity and origin positions.
The input signals that indicate the origin position can be received from the
servomotor's built-in phase-Z signal or external sensors such as photoelectric
sensors, proximity sensors, or limit switches.
Several origin search patterns can be selected.
In the following example, the motor is started at a specified speed, acceler-
ated to the origin search high speed, and run at that speed until the origin
proximity position is detected. After the Origin Proximity Input is detected, the
motor is decelerated to the origin search low speed and run at that speed until
the origin position is detected. The motor is stopped at the origin position.
Pulse frequency
Origin search
initial speed
Origin search
acceleration rate
Origin search
high speed
Deceleration
point
Origin search
deceleration rate
Origin search
proximity speed
Start
Execution of ORG(889)
Decelerate from high to low speed.
Indicated by the Origin
Proximity Input Signal
Stop
Indicated by the
Origin Input Signal
Time
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......