Failure Diagnosis Functions
Section 8-8
8-8-3
Simulating System Errors
FAL(006) and FALS(007) can be used to intentionally create fatal and non-
fatal system errors. This can be used in system debugging to test display
messages on Programmable Terminals (PTs) or other operator interfaces.
Use the following procedure.
1,2,3...
1.
Set the FAL or FALS number to use for simulation in A529. A529 is used
when simulating errors for both FAL(006) and FALS(007).
2.
Set the FAL or FALS number to use for simulation as the first operand of
FAL(006) or FALS(007).
3.
Set the error code and error to be simulated as the second operand (two
words) of FAL(006) or FALS(007). Indicate a nonfatal error for FAL(006)
and a fatal error for FALS(007).
To simulate more than one system error, use more than one FAL(006) or
FALS(007) instruction with the same value in A529 and different values for the
second operand.
Auxiliary Area Flags and Words
Example for a Battery Error
Note
Use the same methods as for actual system errors to clear the simulated sys-
tem errors. Refer to the 12-2 Troubleshooting for details. All system errors
simulated with FAL(006) and FALS(007) can be cleared by cycling the power
supply.
8-8-4
Output OFF Bit
As an emergency measure when an error occurs, all outputs from Output
Units can be turned OFF by turning ON the Output OFF Bit (A500.15). The
operating mode will remain in RUN or MONITOR mode, but all outputs will be
turned OFF.
Note
Normally (when IOM Hold Bit = OFF), all outputs from Output Units are turned
OFF when the operating mode is changed from RUN/MONITOR mode to
PROGRAM mode. The Output OFF Bit can be used to turn OFF all outputs
without switching to PROGRAM mode.
Name
Address
Operation
FAL/FALS Number
for System Error
Simulation
A529
Set a dummy FAL/FALS number to use to simu-
late a system error.
0001 to 01FF hex: FAL/FALS numbers 1 to 511
0000 or 0200 to FFFF hex: No FAL/FALS number
for system error simulation.
MOV
&100
A529
a
MOV
#00F7
D10
FAL
100
D10
Execution condition
Set FAL number 100 in A529.
Set error code for battery error
(#00F7) in D10.
Generate a battery error using FAL
number 100.
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......