233
High-speed Counters
Section 7-1
Starting Interrupt Tasks based on Comparison Conditions
Data registered in advance in a comparison table can be compared with the
actual counter PVs during operation. The specified interrupt tasks (registered
in the table) will be started when the corresponding comparison condition is
met.
There are two comparison methods available: Target value comparison and
range comparison.
• Use the CTBL(882) instruction to register the comparison table.
• Use either the CTBL(882) instruction or INI(880) instruction to start the
comparison operation.
• Use the INI(880) instruction to stop the comparison operation.
Target Value Comparison
The specified interrupt task is executed when the high-speed counter PV
matches a target value registered in the table.
• The comparison conditions (target values and counting directions) are
registered in the comparison table along with the corresponding interrupt
task number. The specified interrupt task will be executed when the high-
speed counter PV matches the registered target value.
• Up to 48 target values (between 1 and 48) can be registered in the com-
parison table.
• A different interrupt task can be registered for each target value.
• The target value comparison is performed on all of the target values in the
table, regardless of the order in which the target values are registered.
• If the PV is changed, the changed PV will be compared with the target
values in the table, even if the PV is changed while the target value com-
parison operation is in progress.
Restrictions
A comparison condition (target value and count direction) cannot appear in
the table more than once. An error will occur if a comparison condition is
specified two or more times.
Note
When the count direction (incrementing/decrementing) changes at a PV that
matches a target value, the next target value cannot be matched in that direc-
tion.
No. 001 No. 015 No. 000
No. 020
High-speed counter PV
Comparison is
executed without
regard to the order
of the values in the
table.
Target value 1
Target value 2
Target value 3
Target value 4
Interrupt task that is started.
Time
Comparison table
Number of values = 4
Target value 1 (Incrementing)
Interrupt task = 000
Target value 2 (Incrementing)
Interrupt task = 001
Target value 3 (Decrementing)
Interrupt task = 020
Target value 4 (Incrementing)
Interrupt task = 015
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......