541
Temperature Sensor Units
Section 9-5
Input Word
Output Word
Read/Response Command and Temperature Data
• Negative values are stored as 2’s complements.
• The converted temperature data CIO m+2 is stored in 16-bit binary data
(4-digit hexadecimal).
• Data for range codes that include one digit after the decimal point are
stored without the decimal point, i.e., 10 times the actual value is stored.
• If the input temperature exceeds the maximum or minimum value in the
temperature input range that has been set by ±20
°
C or ±20
°
F, the dis-
played value will be held.
• If the circuit is disconnected, the open-circuit detection function will oper-
rate and the converted temperature data will be set to 7FFF.
• The open-circuit detection function will be automatically cleared and nor-
mal input temperature conversion will begin automatically when the input
temperature returns to the convertible range.
m+1
Response. Input words stored in CIO m+2
m+2
Temperature data of the specified input word
n+1
Read command data (input word specified)
Command
Output
Word
Input Word
n+1
m+1
m+2
Read
command
Response
command
Temperature data
(4-digit hexadecimal)
Read temperature data from input 0 #9901
9901
Input 0 temperature data
Read temperature data from input 1 #9902
9902
Input 1 temperature data
Read temperature data from input 2 #9903
9903
Input 2 temperature data
Read temperature data from input 3 #9904
9904
Input 3 temperature data
Read temperature data from input 4 #9905
9905
Input 4 temperature data
Read temperature data from input 5 #9906
9906
Input 5 temperature data
Read temperature data from input 6 #9907
9907
Input 6 temperature data
Read temperature data from input 7 #9908
9908
Input 7 temperature data
Read temperature data from input 8 #9909
9909
Input 8 temperature data
Read temperature data from input 9 #990A
990A
Input 9 temperature data
Read temperature data from input 10 #990B
990B
Input 10 temperature data
Read temperature data from input 11 #990C
990C
Input 11 temperature data
Others
Others
No response for other commands
Input
Data conversion examples
Unit: 0.1
°
C
K or J
×
10
500.0
°
C
→
5000
→
1388 hex
−
20.0
°
C
→
−
200
→
FF38 hex
−
200.0
°
C
→
−
2000
→
F830 hex
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......