63
Computing the Cycle Time
Section 2-7
Watch Cycle Time
If the cycle time exceeds the watch (maximum) cycle time setting, the Cycle
Time Too Long Flag (A401.08) will be turned ON and PLC operation will be
stopped.
PLC Setup
Related Flags
Cycle Time
Monitoring
The maximum cycle time is stored in A262 and A263 and the present cycle
time is stored in A264 and A265 every cycle.
Related Words
The average cycle time for the past eight cycles can be read from the CX-Pro-
grammer.
Note
The following methods are effective in reducing the cycle time.
• Place tasks that do not need to be executed on standby.
• Use JMP-JME instructions to skip instructions that do not need to be exe-
cuted.
Name
Settings
Default
Enable Watch Cycle
Time Setting
0: Default (1 s)
1: User setting
0000 hex: Watch cycle time of
1 s
Watch Cycle Time
001 to FA0: 10 to 40,000 ms
(10-ms increments)
Name
Address
Description
Cycle Time Too Long
Flag
A401.08
Turns ON if the present cycle time exceeds the
Watch Cycle Time set in the PLC Setup.
Name
Addresses
Description
Maximum Cycle
Time
A262 and
A263
These words contain the maximum cycle time in
increments of 0.1 ms. The time is updated every
cycle and is recorded in 32-bit binary (0 to FFFF
FFFF hex, or 0 to 429,496,729.5 ms). (A263 is
the leftmost word.)
Present Cycle Time
A264 and
A265
These words contain the present cycle time in
increments of 0.1 ms. The time is updated every
cycle and is recorded in 32-bit binary (0 to FFFF
FFFF, or 0 to 429,496,729.5 ms). (A265 is the
leftmost word.)
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......