![Omron CP1L-EL20DR-D Operation Manual Download Page 414](http://html1.mh-extra.com/html/omron/cp1l-el20dr-d/cp1l-el20dr-d_operation-manual_743755414.webp)
380
Interrupt Functions
Section 8-1
Setting the Input Functions in the PLC Setup
Normally, bits CIO 0.04 to CIO 0.09 are used as normal inputs. When using
these inputs for input interrupts, use the CX-Programmer to change the
input’s setting in the PLC Setup.
Procedure
Input terminal
block
CPU Unit
Input interrupt
Task number
Word
Bit
CPU Units with
40 I/O Points
CPU Units with
30 I/O Points
CPU Units with
20 I/O Points
CIO 0
00
Normal input 0
Normal input 0
Normal input 0
---
---
01
Normal input 1
Normal input 1
Normal input 1
---
---
02
Normal input 2
Normal input 2
Normal input 2
---
---
03
Normal input 3
Normal input 3
Normal input 3
---
---
04
Normal input 4
Normal input 4
Normal input 4
Input
interrupt 0
Interrupt
task 140
05
Normal input 5
Normal input 5
Normal input 5
Input
interrupt 1
Interrupt
task 141
06
Normal input 6
Normal input 6
Normal input 6
Input
interrupt 2
Interrupt
task 142
07
Normal input 7
Normal input 7
Normal input 7
Input
interrupt 3
Interrupt
task 143
08
Normal input 8
Normal input 8
Normal input 8
Input
interrupt 4
Interrupt
task 144
09
Normal input 9
Normal input 9
Normal input 9
Input
interrupt 5
Interrupt
task 145
10
Normal input 10
Normal input 10
Normal input 10
---
---
11
Normal input 11
Normal input 11
Normal input 11
---
---
CIO 1
00 to 05
Normal input 12 to 17
Normal input 12 to 17
---
---
---
06 to 11
Normal inputs 18 to 23
---
---
---
---
Select the input interrupts.
• Determine the inputs to be used for input
interrupts and corresponding task numbers.
↓
Wire the inputs.
• Wire the inputs.
↓
Set the PLC Setup.
• Use the CX-Programmer to select the inter-
rupt inputs in the PLC Setup.
↓
Write the ladder program.
• Write the programs for the corresponding
interrupt task numbers.
• Use MSKS(690) to specify up-differentiation
or down-differentiation.
• Use MSKS(690) to enable input interrupts (in
direct mode).
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......