224
High-speed Counters
Section 7-1
7-1-3
Procedure
Select high-speed counter 0 to 3.
Select the pulse input method, reset
method, and counting range.
Select the kind of interrupt (if any).
Wire inputs.
PLC Setup settings
Ladder program
•
Pulse input methods: Differential phase (4x),
Pulse + direction, Up/Down, or Increment
•
Reset methods: Phase-Z + Software reset, Software reset,
Phase-Z + Software reset (continuing comparing),
Software reset (continuing comparing)
•
Counting ranges: Linear mode or Ring mode
•
Enable/disable interrupts
•
Target value comparison interrupt
•
Range comparison interrupt
•
Connect to the terminals (24 VDC input or line-driver)
•
High-speed Counters 0 to 3 Enable/Disable:
•
High-speed Counters 0 to 3Pulse Input Mode:
Differential phase (4x)
Pulse + direction
Up/Down
Increment
•
High-speed Counters 0 to 3 Reset Method:
Phase-Z + Software reset, Software reset, Phase-Z + Software
reset (continuing comparing), Software reset (continuing
comparing)
•
High-speed Counters 0 to 3 Counting Mode:
Linear mode
Ring mode
•
Program the interrupt task (with any interrupt number between 0
and 255) to be executed when using a target value comparison
or range comparison interrupts.
•
Register a target value comparison table and start the
comparison.
•
Register a range comparison table and start the comparison.
•
Register a target value comparison table without starting the
comparison.
•
Register a range comparison table without starting the
comparison.
•
Change the counter PV.
•
Start comparison with the registered target value comparison
table or range comparison table.
•
Read the high-speed counter PVs, read the status of the high-
speed counter comparison operation, or read the range-
comparison results.
•
Turn ON the High-speed Counter Gate Bit to stop counting input
pulses.
•
High-speed counters 0 to 3: 24 VDC input,
Response frequency: 100 kHz for single-phase, 50 kHz for
differential phase
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......