603
LCD Option Board Function
Section 11-6
14. Press the
Down
or
Up
button to select the display format &.
15. Use the
Forward
button to move the column cursor to the data length position.
The present setting is W.
Select the data length in the following table.
16. Use the
Forward
button to move the column cursor to the position of
Name.
17. Use the
Down
or
Up
button to select the character of each digit.
Name the word to Counter.
Note
1. When selecting the character of the next digit, the leading charac-
ter will be the character of the digit before.
2. The max length of word or bit name is 7 characters.
18. Press the
OK
button to save the setting.
19. Press the
ESC
or
OK
button to return to the User Monitor Setup Screen.
20. Press the
ESC
button three times to return to the Monitor Mode.
Switch to the User Monitor Screen 2 with the
Down
button.
Note
1.
Setting of word or bit name is not necessary. The default name is NULL,
and the memory address will be displayed at the name position in the User
Monitor Screen.
2.
One line setting will take 1 or 2 lines of space. If word or bit name length is
more than 5 characters or data length is a LongWord, it will take 2 lines of
space.
3.
One screen only has 4 lines of space available. If one line setting has al-
ready taken 2 lines of space, the next line setting will be invalid. If the set-
ting of line 4 takes 2 lines of space, its setting will be invalid.
Data length
Meaning
W
One word data
LW
Two word data
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......