59
Power OFF Operation
Section 2-6
The following timing chart shows the CPU Unit power OFF operation in more
detail.
Power OFF Timing Chart
Description of Operation
Power OFF will be detected if the DC power supply falls below 85% of the
rated voltage for the power OFF detection time (2 ms minimum for DC
power). The CPU reset signal will turn ON while the internal power supply is
being held and the CPU Unit will be reset.
2-6-2
Instruction Execution for Power Interruptions
If power is interrupted and the interruption is detected when the CPU Unit is
operating in RUN or MONITOR mode, the instruction currently being executed
will be completed and then the CPU Unit will be reset.
Power OFF detection time:
The time from when the power supply voltages drops to 85% for DC power until the
power OFF condition is detected.
Holding time for 5 V internal power supply after power OFF detection:
The maximum time that the 5 V internal power supply voltage will be maintained after
the power OFF condition is detected. The holding time is fixed at 1 ms.
DC: 85% of rated voltage
Operation always stopped
at this point regardless.
Power OFF detected signal
Program execution status
CPU reset signal
Cyclic tasks or interrupt tasks
Stopped
Power OFF detected
Power OFF Detection
Delay Time
DC: 2 ms
Holding time for 5 V internal
power supply after power
OFF detection: 1 ms
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......