747
Appendix F
Connections to Serial Communications Option Boards
Connection Methods
Communications Modes and Ports
The following table shows the relationship between the communications ports and the communications modes
for the Serial Communications Option Boards.
Note
(1) The NT-AL001 Link Adapter can be used to convert between RS-232C and RS-422A/485 to enable
1:N communications.
(2) Use 4-wire connections between Link Adapters.
Models of Serial Communications Option Board
Note
The CP1W-CIF11 is a non-isolated board, so the maximum transmission distance is 50 m. For distances
over 50 m, use the RS-232C port on the CP1W-CIF01 and then connect through the NT-AL001 Link
Adapter, which is isolated. Doing so will enable a maximum transmission distance of 500 m.
Communications mode
RS-232C
CP1W-CIF01
RS-422A/485
CP1W-CIF11/CIF12
1:1
1:N
(See note 1.)
1:1 4-wire
1:N 4-wire
1:1 2-wire
1:N 2-wire
Host Link
YES
YES
(See note 2.)
YES
YES
No
No
Serial PLC Links
YES
YES
YES
YES
YES
YES
Serial Gateway
YES
YES
YES
YES
YES
YES
No-protocol
YES
YES
YES
YES
YES
YES
1:N NT Link
YES
YES
YES
YES
YES
YES
1:1 NT Link
YES
No
YES
No
YES
No
1:1 Link Master
YES
No
YES
No
YES
No
1:1 Link Slave
YES
No
YES
No
YES
No
Model
Port
Maximum transmission
distance
Connection method
CP1W-CIF01
One RS-232C port
15 m
Connector (D-sub, 9-pin female)
CP1W-CIF11
One RS-422A/485 port
50 m (See note.)
Terminal block (using ferrules)
CP1W-CIF12
One RS-422A/485 port
500 m
Terminal block (using ferrules)
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......