347
Inverter Positioning
Section 7-3
■
Inverter Positioning 1
Use one of the following for the inverter frequency command.
A276 00 to 15 Lower 4 digits of the
present value of the
internal pulse output
(absolute value for
absolute coordi-
nates)
8000 0000 to 7FFF
FFFF hex
(
−
2,147,483,648 to
2,147,483,647)
Contains absolute movement value
from the internal pulse origin when
pulses are output to error counter.
Cleared to zero at following times:
• When power to CPU Unit is turned ON
• When operation is started
Updated at following times:
• Cyclically on error counter cycle
This value can be
used to monitor the
present value of
the internal pulse
output as an abso-
lute value when
using absolute
coordinates.
A277 00 to 15 Upper 4 digits of the
present value of the
internal pulse output
(absolute value for
absolute coordi-
nates)
Word
Bits
Function
Data range
Refresh timing
Application
examples
Word
Bits
Function
Data range
Refresh timing
Application
examples
A30
00 to 15 Lower 4 digits of
present value of
unsigned output
value (output value =
present value of
error counter
×
error
counter cycle (s)
×
gain)
Note
The maxi-
mum and min-
imum output
values are
applied.
0000 0000 to 8000
0000 hex
(0 to
2,147,483,648)
Cleared to zero at following times:
• When power to CPU Unit is turned ON
• At start of operation
• When an error counter error occurs
Updated at following times:
• Cyclically according to error counter
cycle
This value can be
used when not
using automatic
frequency com-
mand calculations
and instead to con-
vert the output
value provided
here in the user
program for output
to the inverter.
This value is used
when signed data
is not required, i.e.,
when using com-
munications or nor-
mal I/O to specify
the direction.
A31
00 to 15 Upper 4 digits of
present value of
unsigned output
value (output value =
present value of
error counter
×
error
counter cycle (s)
×
gain)
Note
The maxi-
mum and min-
imum output
values are
applied.
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......