340
Inverter Positioning
Section 7-3
Refer to 9-3 Analog Output Units for operating procedures for the Analog Out-
put Unit.
■
Calculation Example
Conditions
Inverter’s maximum output frequency: 60 Hz
Calculation
The stored analog output value is calculated as follows:
Stored analog
output value
Inverter frequency
command value (Hz)
Inverter's max. output frequency (Hz)
6,000
CP1L-EL/EM
Automatic
calculations
Inverter
frequency
command value
Auxiliary Area
A23/A33
6,000
Inverter maximum
output frequency (Hz)
Stored analog
output value
Analog output
Unit: 0.01 Hz
1
100
Converting values in A23/A33 to Hz.
Converted in ladder program
Stored analog
output value
60
6,000
1
Auxiliary Area
A23/A33
(Unit: 0.01 Hz)
Auxiliary Area
A23/A33
(Unit: 0.01 Hz)
100
1
Summary of Contents for CP1L-EL20DR-D
Page 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Software Licenses and Copyrights 7...
Page 192: ...158 Trial Operation and Debugging Section 5 3...
Page 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Page 666: ...632 Trouble Shooting Section 11 7...
Page 696: ...662 Standard Models Appendix A...
Page 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Page 836: ...802 PLC Setup Appendix G...
Page 838: ...804 TCP Status Transitions Appendix H...
Page 840: ...806 Ethernet Network Parameters Appendix I...
Page 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Page 844: ...810 Ethernet Specifications Appendix K...
Page 851: ...Index 817 work words 118 write protection 447...
Page 852: ...818 Index...
Page 854: ...820 Revision History...
Page 855: ......